| 2004-06-18 00:00:00 | DENIED: | | | 1.SYSTEMS WITH THE DESIGN CAPACITY | | | GREATER THAN 2,000 CFM SHALL HAVE DUCT | | | SMOKE DETECTORS IN THE SUPPLY AIR DUCT. | | | | | | 2.FAN SHUTDOWN SHALL HAVE NOTIFICATION | | | TO ALARM/STROBE IN NORMALLY OCCUPIED | | | AREAS PER NFPA 90A 6.4.4.3 (1). | | | | | | 3.PER COMMENTS BY ASST FIRE MARSHAL, | | | MIKE CARSILLO MECHANICAL ROOM SHALL BE | | | 1 HR FIRE RATING.FIRE DAMPERS WILL BE | | | REQUIRED. | | | | | | 4.SEE COMMENT #7 BY DEWEY PALMER, | | | ELECTRICAL PLAN REVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|