| 2004-06-10 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED | | | IN PROJECT BOX. SHOULD READ NFPA 101, | | | LIFE SAFETY CODE 2000 EDITION. | | | | | | 2) THE PROPOSED FIRE HYDRANT SHOULD | | | BE LOCATED CLOSER TO THE DRIVEWAY | | | OPENING. THE LOCATION SHOWN WOULD | | | BE DIFFICULT TO USE. | | | | | | 3) TWO DIFFERENT OCCUPANT LOADS ARE | | | REFLECTED IN PLANS. PLEASE CLARIFY. | | | | | | 4) WET FIRE HYDRANTS ARE REQUIRED | | | PRIOR TO, DURING AND AFTER CONSTRUCTION. | | | | | | 5) SUITABLE ROADS ARE TO BE PROVIDED | | | DURING CONSTRUCTION. | | | | | | 6) SINCE THE BUILDING WILL NOT BE | | | FIRE SPRINKLER PROTECTED, THE | | | ELECTRICAL ROOM AND MECHANICAL ROOM | | | SHALL BE AT LEAST ONE HOUR FIRE | | | RATED. | | | | | | 7) THE BUILDING ADDRESS IS REQUIRED. | | | A MINIMUM OF 6" HIGH NUMBERS ARE | | | REQUIRED. | | | | | | 8) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILING. | | | | | | 9) PLEASE INDICATE FIRE EXTINGUISHER | | | LOCATIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|