Plan Review Notes
Plan Review Notes For Permit 04060275
Permit Number 04060275
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-16 00:00:00********** UNSAT ****************
  
 1)NOTE: PLEASE SEE PH-1 AND E-SP.
 PLEASE CORRELATE INFORMATION FOR WIND
 LOADS. PLEASE ALSO PROVIDE INFORMATION/
 WIND LOADS FOR THESE AT THIS TIME.
 CALCS ARE REQUIRED TO BE SIGNED, DATED
 AND SEALED. FS 471.025
 PLEASE ALSO SEE PH-1 MENTIONS ONE OF
 THE "HANDHOLE" BELOW GRADE? PLEASE SEE
 ANY WIRING REQUIRING TO BE ACCESSED
 SHALL NOT BE BELOW GRADE AS IT IS SHOWN
 BEING INCASED IN CONCRETE?
 PLEASE ALSO SEE PLANS MENTIONS TO HAVE
 POWER ALSO CONNECTED TO EM POWER FROM
 PUBLIX GENERATOR SYSTEM. THIS IS NOT
 PERMITTED. POLES MAY BE FED FROM AN
 EMERGANCY SYSTEM PROVIDED AT BANK BUT
 NOT FROM SEPARTE SERVICE FROM PUBLIX.
 PLANS AS SHOWN HAS THE POTENIAL OF
 POWER COMING INTO POLES FROM TWO
 SEPARATE SERVICES AT THE SAME TIME.
 PLEASE SEE NOTES ON THIS SAME SHEET
 ONLY GO THROUGH NOTE#7, NOTES 8,9 AND 10
 SEEM TO BE MISSING AS SHOWN ON DETAIL.
  
 2)NOTE: PLEASE VERIFY IF MCB SHOWN AS
 SHUNT TRIP HAS THE REQUIRED MANUAL MEANS
 OF DISCONNECT PER 230.76/230.79
  
 3)NOTE: PLEASE VERIFY NOTE #6 TO RISER,
 MENTIONS MORE CONDUCTORS NEEDED AND
 NOT CLEAR WHAT THESE "EXTRA" CONDUCTORS
 ARE FOR?
  
 4)NOTE: PLEASE SEE "GROUNDING GEN NOTE"
 MENTIONS GROUNDING ELECTRODE CONDUCTOR
 IS TO BE CONTINUOUS AS REQUIRED UNDER
 NEC 250.64C, HOWEVER PLANS SHOW GEC
 GOING TO GROUND BAR SEPARATELY??
 PLEASE CLARIFY.
  
 5)NOTE: PLEASE SEE A COUPLE OF LOCATIONS
 ON PLANS WHERE THE CODES REFERENCED ARE
 FROM THE 96 NEC. PLEASE SEE WE ARE UNDER
 THE 2002 NEC.
  
 6)NOTE: PLEASE SHOW LOAD CALCULATIONS
 FOR INDIVIDUAL PANELS. 215.5/220
 UNABLE TO VERIFY AT THIS TIME.
  
 7)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 ON TITLE BLOCK AS REQUIREDUNDER
 FAC 61G15-23.002, FS 471.023.
 PLEASE SEE THIS INFORMATION IS REQUIRED
 FOR ALL SHEETS, WHEATHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWERS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET IF OLD/VOIDED SHEETS MAY BE
 SENT BACK IN FOR REFERENCE ONLY.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.