 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GENERATOR OUTPUT RATING FOR
 NATURAL GAS IS 125 AMPS IN THE
 SPECIFICATIONS. THE CALCULATIION FOR THE
 LOAD SERVED IS 170.4 AMPS. THE SYSTEM
 SHALL HAVE ADEQUATE CAPACITY AND RATING
 FOR THE SUPPLY OF ALL EQUIPMENT SERVED
 PER 702.5.
  
 2} THE GROUNDING ELECTRODE CONDUTOR MUST
 BE CONTINUOUS PER 250.64(C), AND SIZED
 PER 250.66. THIS COMMENT WAS REDLINED ON
 THE ORIGINAL PLAN. THE #2 GEC TO THE
 COLD WATER BOND, AND THEN A SEPARATE #4
 TO THE SUPPLEMENTARY ELECTRODE AND
 FOOTER STEEL IS IN VIOLATION. THE #2
 CONTINUOUS GEC IS REQUIRED FOR THE
 SERVICE SIZE.
 PLEASE CORRECT.
  
 3} PLEASE SHOW THE LOCATION OF ALL
 SERVICE EQUIPMENT AND GENERATOR
 EQUIPMENT ON THE PLAN. ATS, DISCONNECT,
 ETC.
  
 4} PLEASE FIELD VERIFY THE LOCATION OF
 THE RECEPTACLE IN THE NORTH EAST WALL OF
 BEDROOM #2 AS IT DOES NOT MEET THE
 SPACING REQUIREMENTS OF ARTICLE
 210.52(A)(1). THIS WAS REDLINED ON THE
 REVIEWED PLANS AS WELL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  