| Plan Review Notes For Permit 04060240 |
| Permit Number |
04060240 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-09-21 00:00:00 | ********* UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE PREVIOUS PLANS SHOW | | | EXSITING ELECTRICALWHICH IS NOW MISS- | | | -ING FROM THESE PLANS. | | | PLEASE ALSO SEE MISSING PANEL SCHEDULE. | | | | | | 2)NOTE: PLEASE SEE NOW NEW ITEMS ARE | | | BEING ADDED TO BATHS ETC. | | | PLEASE SEE 210.52D,210.11C3 FOR BATH | | | CIRCUIT TO BE 20A #12. | | | | | | 3)NOTE: PLEASE SEE SCOPE OF WORK HAS | | | ALSO INCREASED. VALUE MUST BE INCREASED | | | PER FBC 104.6.5 | | | | | | 4)NOTE: PLEASE SEE FBC CHAPTER 34 WHICH | | | REQUIRES BRINGING ELECTRICAL UP TO CODE | | | FOR ALTERATIONS AND % OF REMODEL. | | | PLEASE SEESD'S INSIDE AND OUTSIDE | | | BEDRMS WILL BE REQUIRED ALONG WITH GFI'S | | | IN ANY LOCATIONS WHERE REQUIRED AND NOT | | | EXISTING.210.8 | | | | | | 5)NOTE: PLEASE SUBMIT TWO COPIES OF | | | PLANS FOR REVIEW AND STAMPING . | | | FBC 104.2.1 | | | | | | PLEASE SEE POSSIBLE COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|