Plan Review Notes
Plan Review Notes For Permit 04060232
Permit Number 04060232
Review Stop E
Sequence Number 5
Notes
Date Text
2004-09-17 00:00:00********* UNSAT 5TH REVIEW **********
  
 PLEASE SEE THERE ARE STILL COMMENTS FROM
 THE FOUR PREVIOUS REVIEWS WHICH MUST BE
 CORRECTED.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 THE AVAILABLE FAULT CURRENT IS SHOWN
 ON PLANS FROM FPL,HOWEVER THIS DOES NOT
 GIVE THE RATING OF EQUIPMENT.
  
 2)NOTE: PLEASE SEE RISER AND PLANS SHOWS
 A MAIN DISC TO BE INSTALLED BETWEEN
 METER AND MAIN, YET NO INFORMATION ON
 THIS DISCONNECT OS SHOWN.
 PLEASE ALSO SEE IF A MAIN DISC IS
 INSTALLED BEFORE PANEL(IF REQUIRED) THEN
 AN EQUIPMENT GROUNDING CONDUCTOR FROM
 MAIN TO PANEL IS REQUIRED.
 250.24,250.110,250.122
  
 3)NOTE:
  
 4 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
 ARC FAULT IS LISTED FOR ONE CIRCUIT
 ONLY, THIS IS REQUIRED FOR ALL SLEEPING
 RMS. PLEASE SEE ONE CIRCUIT WOULD NOT
 FEED ALL SLEEPING RMS.
  
 5)NOTE: PLEASE SHOW LOCATIONS FOR ALL
 SERVICE EQUIPMENT ON PLANS. MAINS/
 ETC.215.5
  
 6)NOTE: PLEASE SEE 104.2.1. PLANS
 MUST HAVE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS.
  
 7)NOTE: PLEASE SEE PLANS ARE NOW MISSING
 PANEL SCHEDULE SHOWING MIN CIRCUITS
 REQUIRED UNDER NEC.210.52,210.11,220.16
 ETC.
  
 AN ADDITIONAL 10% RE-SUB WILL BE DUE
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]