| 2004-09-17 00:00:00 | ********* UNSAT 5TH REVIEW ********** |
| | |
| | PLEASE SEE THERE ARE STILL COMMENTS FROM |
| | THE FOUR PREVIOUS REVIEWS WHICH MUST BE |
| | CORRECTED. |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | THE AVAILABLE FAULT CURRENT IS SHOWN |
| | ON PLANS FROM FPL,HOWEVER THIS DOES NOT |
| | GIVE THE RATING OF EQUIPMENT. |
| | |
| | 2)NOTE: PLEASE SEE RISER AND PLANS SHOWS |
| | A MAIN DISC TO BE INSTALLED BETWEEN |
| | METER AND MAIN, YET NO INFORMATION ON |
| | THIS DISCONNECT OS SHOWN. |
| | PLEASE ALSO SEE IF A MAIN DISC IS |
| | INSTALLED BEFORE PANEL(IF REQUIRED) THEN |
| | AN EQUIPMENT GROUNDING CONDUCTOR FROM |
| | MAIN TO PANEL IS REQUIRED. |
| | 250.24,250.110,250.122 |
| | |
| | 3)NOTE: |
| | |
| | 4 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 NEC 210.12 |
| | ARC FAULT IS LISTED FOR ONE CIRCUIT |
| | ONLY, THIS IS REQUIRED FOR ALL SLEEPING |
| | RMS. PLEASE SEE ONE CIRCUIT WOULD NOT |
| | FEED ALL SLEEPING RMS. |
| | |
| | 5)NOTE: PLEASE SHOW LOCATIONS FOR ALL |
| | SERVICE EQUIPMENT ON PLANS. MAINS/ |
| | ETC.215.5 |
| | |
| | 6)NOTE: PLEASE SEE 104.2.1. PLANS |
| | MUST HAVE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR PLANS. |
| | |
| | 7)NOTE: PLEASE SEE PLANS ARE NOW MISSING |
| | PANEL SCHEDULE SHOWING MIN CIRCUITS |
| | REQUIRED UNDER NEC.210.52,210.11,220.16 |
| | ETC. |
| | |
| | AN ADDITIONAL 10% RE-SUB WILL BE DUE |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |