Plan Review Notes
Plan Review Notes For Permit 04060232
Permit Number 04060232
Review Stop E
Sequence Number 4
Notes
Date Text
2004-08-18 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 2} INDICATE THE SPECIFICATIONS FOR THE
 SERVICE TO BE INSTALLED FOR THIS
 PROJECT, WIRE & CONDUIT TYPE AND SIZE.
 REMOVE INFORMATION FROM THE RISER THAT
 IS NOT PERTINENT.
  
 3} SHOW THE LOCATION OF ALL SERVICE
 EQUIPMENT ON THE DRAWING. IF THE
 DISCONNECT IS TO BE INSTALLED INDICATE
 SAME. SEE WPB AMMENDMENT 230.70 FOR
 REQUIREMENT.
  
 4} THE LOAD CALCULATION & PANEL CIRCUIT
 NUMBERS, WIRE AND OCP SIZES DO NOT
 CORRELATE WITH THE PANEL SCHEDULE.
  
 5} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.11(C)(3).
  
 6} THE NOTE AT THE BOTTOM OF THE PAGE
 IS INCORRECT, PLEASE REFERENCE THE 2002
 NECARTICLE 250.50 AND 250.66.
  
 ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. SECTION
 104.2.1
  
 FOUR OF THE SIX COMMENTS LISTED IN THIS
 REVIEW WERE ON THE LAST REVIEW. IF THERE
 ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved