| Plan Review Notes For Permit 04060232 |
| Permit Number |
04060232 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-07-28 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING | | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | | CURRENT PER 110.9. | | | | | | 2} INDICATE THE AMPERAGE OF THE SERVICE | | | TO BE INSTALLED, WIRE AND CONDUIT SIZE | | | AND TYPE. | | | | | | 3} INDICATE IF DISCONNECT SHOWN ON THE | | | RISER IS TO BE INSTALLED. SEE 230.70 | | | WPB AMMENDMENTS. | | | | | | ALL INFORMATION/DRAWINGS/SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON | | | RESPON-SIBLE FOR THE DESIGN. SECTION | | | 104.2.1 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|