Plan Review Notes
Plan Review Notes For Permit 04060232
Permit Number 04060232
Review Stop E
Sequence Number 3
Notes
Date Text
2004-07-28 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 2} INDICATE THE AMPERAGE OF THE SERVICE
 TO BE INSTALLED, WIRE AND CONDUIT SIZE
 AND TYPE.
  
 3} INDICATE IF DISCONNECT SHOWN ON THE
 RISER IS TO BE INSTALLED. SEE 230.70
 WPB AMMENDMENTS.
  
 ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPON-SIBLE FOR THE DESIGN. SECTION
 104.2.1
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  