Plan Review Notes
Plan Review Notes For Permit 04060232
Permit Number 04060232
Review Stop E
Sequence Number 2
Notes
Date Text
2004-07-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 2} INDICATE THE AMPERAGE RATING OF THE
 SERVICE. 215.5.
  
 3} INDICATE THE LOCATION OF ALL SERVICE
 EQUIPMENT ON THE DRAWING.
  
 4} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 5} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.11(C)(3).
  
 6} THE ISLAND IN THE KITCHEN MUST COMPLY
 WITH 210.52(C)(2), AND BE GFI PER
 210.8(6).
  
 7} THE RECEPTACLE SPACING FOR THE MASTER
 BATH COUNTERTOP DOES NOT COMPLY WITH
 210.52(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL .
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026