| 2004-07-09 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING | | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | | CURRENT PER 110.9. | | | | | | 2} INDICATE THE AMPERAGE RATING OF THE | | | SERVICE. 215.5. | | | | | | 3} INDICATE THE LOCATION OF ALL SERVICE | | | EQUIPMENT ON THE DRAWING. | | | | | | 4} PLEASE LIST THE REQUIRED ARC | | | FAULT PROTECTED CIRCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | | | 5} PLEASE LIST ALL THE REQUIRED | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.11(C)(3). | | | | | | 6} THE ISLAND IN THE KITCHEN MUST COMPLY | | | WITH 210.52(C)(2), AND BE GFI PER | | | 210.8(6). | | | | | | 7} THE RECEPTACLE SPACING FOR THE MASTER | | | BATH COUNTERTOP DOES NOT COMPLY WITH | | | 210.52(D). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL . | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|