Plan Review Notes
Plan Review Notes For Permit 04060232
Permit Number 04060232
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 2} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.11(C)(3).
  
 3} THE GROUNDING SYSTEM NOTE REFERS
 INCORRECTLY TO 1996 NEC. PLEASE NOTE
 THE STATE OF FLORIDA ADOPTED THE 2002
 NEC IN JUNE 2003.
  
 4} PLEASE SEE MISSING RECEPTACLE,
 FRONT AND/OR REAR OF DWELLING.
 210.52(E).
  
 5} PLEASE SEE RECEPTACLES SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52(C)-
 SEC'S 1,2,3,4 AND 5.
  
 6} THE RECEPTACLE SPACING AT THE MASTER
 BATH COUNTERTOP MUST COMPLY WITH
 210.52(D).
  
 7} THE SMOKE DETECTOR IN THE HALL BY THE
 BATHROOM (#2) MUST BE 3' MIN. AWAY TO
 COMPLY WITH 8-1.4.2. NFPA-72.
  
 ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPON-
 SIBLE FOR THE DESIGN. SECTION 104.2.1
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved