| Date |
Text |
| 2004-06-09 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT PER 110.9. |
| | |
| | 2} PLEASE LIST ALL THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.11(C)(3). |
| | |
| | 3} THE GROUNDING SYSTEM NOTE REFERS |
| | INCORRECTLY TO 1996 NEC. PLEASE NOTE |
| | THE STATE OF FLORIDA ADOPTED THE 2002 |
| | NEC IN JUNE 2003. |
| | |
| | 4} PLEASE SEE MISSING RECEPTACLE, |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52(E). |
| | |
| | 5} PLEASE SEE RECEPTACLES SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52(C)- |
| | SEC'S 1,2,3,4 AND 5. |
| | |
| | 6} THE RECEPTACLE SPACING AT THE MASTER |
| | BATH COUNTERTOP MUST COMPLY WITH |
| | 210.52(D). |
| | |
| | 7} THE SMOKE DETECTOR IN THE HALL BY THE |
| | BATHROOM (#2) MUST BE 3' MIN. AWAY TO |
| | COMPLY WITH 8-1.4.2. NFPA-72. |
| | |
| | ALL INFORMATION/DRAWINGS/SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPON- |
| | SIBLE FOR THE DESIGN. SECTION 104.2.1 |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |