| Date |
Text |
| 2004-06-04 00:00:00 | *********** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | THIS IS REQ'D FOR NEW SERVICE BEING |
| | SHOWN. |
| | |
| | 2) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 3) NOTE: PLEASE SHOW GROUNDING ELETRODE |
| | SYSTEM PER 250.50. FOOTER STEEL/COLD |
| | WATER/ ETC. SIZE ALL PER 250.66 |
| | |
| | 4) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 5 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 6 )NOTE: PLEASE CORRELATE RISER DIGRAM(S |
| | WITH PANEL SCHEDULE(S). |
| | |
| | 7) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 8 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 9)NOTE: PLEASE SEE FBC CHAPTER 34 FOR |
| | ADDTIONS TO EXISTING DWELLINGS MORE THAN |
| | 25%. |
| | |
| | 10)NOTE: PLEASE SEE MISSING REQ'D EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210.70 AND LS-101 5-8 |
| | |
| | 11)NOTE: PLEASE SHOW /CLARIFY METHOD |
| | OF THE EQUIPMENT GROUNDING BETWEEN |
| | MAIN MEANS OOF DISC AND PANELS/GUTTERS. |
| | 250.110,250.24 |
| | PLEASE SIZE ALL EQUIPMENT GROUNDING |
| | CONDUCTORS PER 250.122 |
| | |
| | 12)NOTE: PLEASE INCLUDE ALL LICENSE |
| | #'S ON THE REQ'D TITLE BLOCK. |
| | PLEASE ALSO INCLUDE CERTIFICATE OF |
| | AUTHORIZATION #'S WHERE REQ'D. |
| | |
| | PER FS 471.023, FAC 61G15-23.002 (ENG'S) |
| | PER FS 481.219, FAC 61G1-16.004 (ARCH'S) |
| | |
| | 13)NOTE: PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |