| Plan Review Notes For Permit 04060157 |
| Permit Number |
04060157 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-08-03 00:00:00 | | | | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | NOTE THAT ON SHEET E-1 THE FOLLOWING | | | ITEMS NEED CORRECTIONS. | | | | | | 1} THE BEDROOM NEEDS TWO RECEPTACLES | | | ADDED TO COMPLY WITH 210.52(A)&(B). | | | | | | 2} THE LOCATION OF THE A/C DISCONNECTS | | | DO NOT COMPLY WITH CLEARANCE | | | REQUIREMENTS OF 110.26. | | | | | | PLEASE SEE THAT THESE CORRECTIONS ARE | | | MADE PRIOR TO ROUGH INSPECTION AND | | | REVISED ON THE PLAN BEFORE C.O.. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|