| 2004-06-11 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE ELECTRICAL RISER INDICATES THE | | | SERVICE IS EXISTING. SHOW LOCATION OF | | | SERVICE. THIS IS CONFUSING DO TO THE | | | FACT THE RESIDENCE HAS NOT YET BEEN | | | CONSTRUCTED. | | | | | | 2} PLEASE PROVIDE PANEL SCHEDULES AND | | | LOADS FOR ALL PANELS. WHAT DOES THE 2ND | | | METER AND PANEL "K" SERVE? | | | | | | 3} THE GRONDING ELECTRODE SYSTEM MUST | | | COMPLY WITH 250.50 "EACH ITEM", | | | INCLUDING FOOTER STEEL, (UFER GROUND). | | | | | | 4} THE GARAGE RECEPTACLES MUST BE GFCI | | | PROTECTED PER 210.8(A)(2). | | | | | | 5} PROVIDE SMOKE DETECTORS PER | | | 8-1.4.1.6.2 NFPA-72 & 905.2.2 FBG, SEE | | | SHEET E-1. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|