| 2004-06-07 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING | | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | | CURRENT PER 110.9 NEC. | | | | | | 2} PROVIDE A RISER DIAGRAM PER 215.5, | | | AND INCLUDE GROUNDING DETAIL PER 250.50 | | | & 250.66. | | | | | | 3} THE PERSON RESPONSIBLE FOR THE | | | DESIGN SHALL PUT THEIR NAME AND | | | SIGNATURE ON THE DRAWING PER 104.2.1, | | | FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|