 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9 NEC.
  
 2} PROVIDE A RISER DIAGRAM PER 215.5,
 AND INCLUDE GROUNDING DETAIL PER 250.50
 & 250.66.
  
 3} THE PERSON RESPONSIBLE FOR THE
 DESIGN SHALL PUT THEIR NAME AND
 SIGNATURE ON THE DRAWING PER 104.2.1,
 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  