| Plan Review Notes For Permit 04060123 |
| Permit Number |
04060123 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-11-15 00:00:00 | ******* UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE NOTES ON TWO PREVIOUS | | | REVIEWS REQUESTED ALL OLD/VOIDED SHEETS | | | TO BE REMOVED. PLANS STILL CONTAIN OLD | | | SHEETS IN SETS. | | | ONE SET OF OLD SHEETS SHOULD BE | | | SUBMITTED SEPARATELY. | | | | | | 2)NOTE: PLEASE SEE SHEET HAS NOW BEEN | | | REVISED TO REMOVE EXHAUST FANS, | | | THIS WILL REQUIRE MECH/FIRE REVIEW. | | | PLEASE SEE PLANS ALSO NEED TO CORRELATE | | | WITH PANEL SCHEDULES AND LOAD | | | CALCUALTIONS. PANELS ETC ARE STILL | | | SHOWING THESE?? | | | | | | PLEASE SEE ANY COMMENTS FROM OTHER | | | REVIEWERS WHICH MAY HAVE AN AFFECT ON | | | ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|