Text |
| 2004-07-30 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | |
| | |
| | 1) FROM PREVIOUS REVIEW: SUBMIT CALCUL- |
| | ATIONS FOR PRIMARY AND SECONDARY ROOF |
| | DRAINS. SHOW AREA OF ROOF AND 1/2 AREA |
| | OF ALL VERTICAL WALLS INCLUDING PARAPETS |
| | ADDED TO ROOF AREAS. SECTIONS 1106 AND |
| | 1107. RESPONSE NOTED BUT NO CALCULATIONS |
| | ARE SHOWN. PLEASE CLARIFY. |
| | 5) FROM PREVIOUS REVIEW: SUBMIT CLACUL- |
| | ATIONS FOR PRIMARY AND SECONDARY ROOF |
| | DRAINS FOR THE EXISTING ROOF. SHOW 1/2 |
| | AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS ADDED TO AREA OF ROOF IN THE |
| | CALCULATIONS. SECTIONS 1106 AND 1107 AND |
| | ALL SUBSECTIONS. - NO RESPONSE NOTED. |
| | 7) FROM PREVIOUS REVIEW: SHT 601 SANIT- |
| | ARY RISER DIAGRAM DOES NOT REFLECT THE |
| | LAYOUT. CLEANOUTS NEAR THE BLDG. DRAIN |
| | AND SEWER JUNCTION ARE NOT TWO-WAY ON |
| | THE RISER DIAGRAM. THE LAUNDRY SINK |
| | SHALL NOT DRAIN THROUGH THE WET VENT FOR |
| | THE BATHROOM FIXTURES. THIS SINK SHALL |
| | CONNECT DOWNSTREAM OF THE TOILET ROOM |
| | FIXTURES. SECTION 909.1 - THE WATER |
| | CLOSETS SHALL NOT BE DOUBLE TRAPPED. THE |
| | W/C'S HAVE INTEGRAL TRAPS AND DO NOT RE- |
| | QUIRE A TRAP PRIOR TO THE FIXTURE. SECT- |
| | ION 1002.1 EXCEPTION (1). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |