2004-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) IRRIGATION PLANS/PERMIT REQUIRED.
 2) INDICATE LOCATION OF WATER COOLERS
 ON THE FLOOOR PLAN. SECTION 104.2.1
 3) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW AREA OF ROOF
 AND 1/2 AREA OF ALL VERTICAL WALLS IN-
 CLUDING PARAPETS ADDED TO ROOF AREAS.
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 4) SHT 306 DETAIL #11, OVERFLOW SCUPPER,
 INDICATE WIDTH ON DETAIL TO DETERMINE
 AREA OF SCUPPER. SECTION 104.2.1
 5) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS FOR THE EXISTING
 BLDG. SHOW LOCATION OF PRIMARY AND SEC-
 ONDARY ROOF DRAINS. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED
 TO AREA OF ROOF IN CALCULATIONS. SECTION
 1106 & SECTION 1107 AND ALL SUBSECTIONS.
 6) SHTS 101 AND 600. SHT 101 SHOWS THE
 METER AND BACKFLOW EXISTING, BUT SHT 600
 SHOWS A PRESSURE REDUCING VALVE. PLEASE
 CLARIFY. SECTION 104.2.1.
 7) SHT 601 SANITARY AND WATER RISER DIA-
 GRAMS DO NOT REFLECT THE FLOOR PLAN. MOP
 SINKS ARE NOT SHOWN ON THE RISER. CLEAN-
 OUTS NEAR THE BLDG. DRAIN & BLDG. SEWER
 JUNCTION SHOULD BE 2-WAY CLEANOUTS. SEC.
 708.3.5 - PVC IS NOT APPROVED FOR DIST-
 RIBUTION PIPE. TABLE 605.5 (SEE NOTE #6)
 8) SHT 601, SHOW HEIGHT OF W/C 11-4.16.3
 FLUSH CONTROLS 11-4.16.5 - FOR LAVS SHOW
 CLEARENCES OF 29" 11-4.19.2, AND EXPOSED
 PIPES AND SURFACES 11-4.19.4.
 9) SHTS 300 & 600 FLOOR PLANS SHOW DOORS
 TO TOILET ROOMS SWINGING INTO THE TOILET
 ROOMS. DETAIL #1 SHOWS OUTWARD SWINGS.
 SECTION 11-4.22.2 DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE. CORRELATE FLOOR PLAN AND
 TOILET ROOM DETAIL. SECTION 104.2.1.
 10) A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL DRAWINGS AND MUST CONTAIN
 A) FIRM NAME, ADDRESS, AND TELEPHONE NUM
 BER.
 B) FIRM LICENSE NUMBER
 61G1-16.004(1)(2) & FS 481.2055
 11) UNABLE TO READ THE INFORMATION REQ-
 UIRED TO BE IMPRESSED BY THE SEAL OF THE
 ARCHITECT ON SHEETS 600 & 601.
  
 REVIEW BY KEN STEVENS