| 2004-06-23 00:00:00 | ****CORRECTIONS**** |
| | |
| | *****PAID PLAN CHECK, NOT A PERMIT |
| | APPLICATION***** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)THE CORRECT ADDRESSES OF THE |
| | PARCELS ARE 6501 & 6511 (NOT 6500/6511) |
| | ACCORDING TO THE PROPERTY APPRAISER. |
| | REVISE THE PERMIT APPLICATION AND PLANS. |
| | |
| | 2.)RE: STRUCTURAL CALCULATIONS |
| | PREPARED BY X. CHEN, PE, A TITLE BLOCK |
| | FOR THE ENGINEER IS REQUIRED FAC61G15.23 |
| | .002. |
| | |
| | 3.)RE: STRUCTURAL CALCULATION PREPARED |
| | BY X.CHEN, PE, REVISE THE 4TH SHEET TO |
| | CORRECTLY SHOW ZONE 3, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO THE FBC, TABLE |
| | 2306.1, SEE ATTACHED. |
| | |
| | 4.)PRIOR TO PERMITTING, IMPACT FEES |
| | MUST BE PAID TO PALM BEACH COUNTY.THE |
| | PLANS MUST BE STAMPED AND THE RECEIPT |
| | ATTACHED TO THE APPLICATION.233-5025 |
| | |
| | 5.)PRIOR TO PERMITTING, A NOTICE OF |
| | COMMENCEMENT MUST BE FILED WITH THE |
| | CLERK OF COURTS. |
| | |
| | 6.)PROVIDE A COPY OF THE RECORDED |
| | UNITY OF TITLE. |
| | |
| | 7.)WHEN CONVERTING TO PERMIT, SEPARATE |
| | PERMITS WILL BE REQUIRED FOR THE TWO |
| | DIFFERENT BUILDINGS AND FOR THE |
| | DUMPSTER ENCLOSURE.ADDITIONAL PERMITS |
| | WILL ALSO BE REQUIRED FOR THE FENCE, |
| | GATE AND AWNING. |
| | |
| | 8.)ZONING APPROVAL REQUIRED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 9.)WHITEOUT HAS BEEN USED TO REVISE |
| | A SHEET (102, SEE HIGHLIGHT ON REVIEW |
| | SET).BEFORE RESUBMITTING PLEASE MAKE |
| | REVISIONS TO THE ORIGINAL SET, DO NOT |
| | WHITEOUT CHANGES. |
| | |
| | 10.) SHEET 102, AN ELEVATION OF 17.0 AND |
| | 17.58 ARE GIVEN OUTSIDE OF THE DOOR TO |
| | BLDG 1. |
| | |
| | 11.) SHEET 102, ELEVATION OF FLOOR |
| | SURFACES ON BOTH SIDES OF A DOOR SHALL |
| | NOT VARY BY MORE THAN 1/2, FBC1012.1.3. |
| | |
| | 12.)PROVIDE WIDTH AND SLOPE OF THE ADA |
| | PARKING ACCESS AISLES AND SIDEWALK, |
| | ACCESSIBLE PARKING SPACE FBC CHAPTER 11. |
| | |
| | 13.)SHEET LS OF THE REVIEW SET IS NOT |
| | SIGNED AND SEALED.PLEASE CHECK ALL |
| | SHEETS BEFORE RESUBMITTAL. |
| | |
| | 14.)FOR THE SHEETS SEALED BY AN |
| | ENGINEER, THE TITLE BLOCK IS TO BE IN |
| | COMPLIANCE WITH FAC61G15-23.002. |
| | LACKING FOR STUART CUNNINGHAM PE ARE THE |
| | ADDRESS, CA NUMBER FOR THE COMPANY. |
| | |
| | 15.)FOR THE SHEETS SEALED BY AN |
| | ARCHITECT, A TITLE BLOCK IS REQUIRED |
| | IN ACCORDANCE WITH FAC61G1. |
| | FOR WILLIAM FLINT, ADDRESS REQUIRED. |
| | FOR DON BOITNOIT, CA NUMBER FOR AHRENS. |
| | |
| | 16.)THE TYPICAL H/C PARKING AND |
| | STANDARD PARKING STALLS (SHEET 103) IS |
| | TO COMPLY WITH WPB STANDARD, SEE |
| | ATTACHED. |
| | |
| | 17.) IT APPEARS THAT THE ACCESSIBLE |
| | ROUTE TO BLDG 1 IS BLOCKED BY SOD AND |
| | LANDSCAPING, SHEETS 102 AND 103.THE |
| | ROUTE FOR BLDG 2 IS OFFSET; THE DOOR |
| | SWINGS OVER THE ACCESSIBLE PARKING |
| | SPACE.PLEASE CORRECT AND/OR CLARIFY. |
| | |
| | 18.) TABLE 600 REQUIRES 0% OPENINGS FOR |
| | THE WEST AND SOUTH PROPERTY LINES. BOTH |
| | BUILDINGS SHOW A WALL EXHAUST FAN |
| | (1-500) ON THE WEST SIDE, SHEET 300. |
| | |
| | 19.) SHEET 300, THE BATHROOMS ARE |
| | REQUIRED TO BE ACCESSIBLE.THE DETAIL |
| | 1-304 IS COMPLIANT BUT THE FLOOR PLAN |
| | ON SHEET 300 SHOWS AN INSWING DOOR WHICH |
| | ENCROACHES UPON THE CLEAR FLOOR SPACE |
| | REQUIRED FOR FIXTURES FBC11-4.23.3. |
| | |
| | 20.) SPECIFY INSULATION R VALUE, 8-306. |
| | |
| | 21.) SHEET 400 SHOWS A LL OF 100#; |
| | FBC TABLE 1604.1 REQUIRES 100 FOR LIGHT |
| | MANUFACTURING, 150 FOR HEAVY. FBC |
| | 1604.3 CONCENTRATED FLOOR LOADS WILL BE |
| | CONSIDERED BUT NOT LESS THAN TABLE1604.1 |
| | INDICATE DESIGN CRITERIA AND SHOW |
| | COMPLIANCE.ALSO SEE STORAGE WAREHOUSE |
| | IN TABLE 1604.1. |
| | |
| | 22.)TEST REPORTS AND FLORIDA STATE, |
| | LOCAL OR SITE SPECIFIC PRODUCT APPROVALS |
| | REQUIRED FOR THE DOORS, LOUVERS, ROLLUP |
| | DOORS, AND ROOF. |
| | WWW.FLORIDABUILDING.ORG FOR THE |
| | FLORIDA STATE PRODUCT APPROVAL. |
| | |
| | 23.)NOTE 7.B.1 INDICATES A HAZARDOUS |
| | OCCUPANCY SEPARATION; CLARIFY AS NO |
| | OCCUPANCY SEPARATIONS ARE SHOWN ON THE |
| | PLAN. |
| | |
| | 24.)NOTE 6.A GIVES A REQUIREMENT OF |
| | 0-400 SMOKE DEVELOPED,, SHOULD BE 0-450 |
| | FBC803.2. |