| Plan Review Notes For Permit 04060031 |
| Permit Number |
04060031 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | 1) PLANS INDICATE 3" PVC VENT PIPE, BUT | | | MANUF. INFORMATION STATES VENT HOODS MAY | | | BE EXTREAMLY HOT DURING OPERATION. | | | PLEASE CLARIFY. SUBMIT MANUF INFO FOR | | | THE VENTING. | | | 2) PIPE SIZE FROM METER TO EXISTING TEE | | | SHALL BE CHANGED TO 1-1/2" PER TABLE | | | 402(2) FOR 620,000 BTU'S @ 50 FEET. | | | 3) ALL INFORMATION, DRAWINGS, SPECIFIC- | | | ATIONS AND ACCOMPANYING DATA SHALL BEAR | | | THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|