Plan Review Notes For Permit 04060018
Permit Number 04060018
Review Stop M
Sequence Number 2
Notes
Date Text
2004-08-25 00:00:00DENIED:
 1.PLANS SUBMITTED FOR REVISION HAVE A
 TITLE BLOCK FOR THE ARCHITECT. PER THE
 FLORIDA STATUTE 481.221 & FLORIDA
 ADMINISTRATIVE CODE 61GG1-16.004,
 ARCHITECT IS TO SIGN, DATE & AFFIX SEAL
 WITH LICENSE NUMBER ON ALL PLANS
 DESIGNED BY THE ARCHITECT.
  
 2.PLEASE CLARIFY THE RETURN AIR FROM
 THE MASTER BEDROOM.REVISED PLAN
 INDICATES A RETURN AIR JUMPER.PER
 THE REVISED 2001 FBC(M) 601.4 EXCEPTION
 #1 & 3, RETURN AIR JUMPERS SHALL BE
 INCREASED TO 1 1/2 TIMES THE SUPPLY AIR
 TO THAT SPACE.ALL AIR INTO THE MASTER
 SUITE IS TO BE INCLUDED FOR PROPER
 SIZING OF THE RETURN AIR JUMPER.THE
 RETURN AIR JUMPER SHALL BE A MINIMUM OF
 16".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.