| Plan Review Notes For Permit 04060018 |
| Permit Number |
04060018 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-08-25 00:00:00 | DENIED: | | | 1.PLANS SUBMITTED FOR REVISION HAVE A | | | TITLE BLOCK FOR THE ARCHITECT. PER THE | | | FLORIDA STATUTE 481.221 & FLORIDA | | | ADMINISTRATIVE CODE 61GG1-16.004, | | | ARCHITECT IS TO SIGN, DATE & AFFIX SEAL | | | WITH LICENSE NUMBER ON ALL PLANS | | | DESIGNED BY THE ARCHITECT. | | | | | | 2.PLEASE CLARIFY THE RETURN AIR FROM | | | THE MASTER BEDROOM.REVISED PLAN | | | INDICATES A RETURN AIR JUMPER.PER | | | THE REVISED 2001 FBC(M) 601.4 EXCEPTION | | | #1 & 3, RETURN AIR JUMPERS SHALL BE | | | INCREASED TO 1 1/2 TIMES THE SUPPLY AIR | | | TO THAT SPACE.ALL AIR INTO THE MASTER | | | SUITE IS TO BE INCLUDED FOR PROPER | | | SIZING OF THE RETURN AIR JUMPER.THE | | | RETURN AIR JUMPER SHALL BE A MINIMUM OF | | | 16". | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|