| Date |
Text |
| 2004-06-18 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) ALL ARCHITECTURAL SHEET SHALL BE SEA- |
| | LED AND DATED PER FAC 61G1-16.003 AND |
| | FS 481.2055. |
| | 2) SHT A-114 SHOW CLEAR FLOOR SPACE FOR |
| | SINK IN BREAK ROOM. SECTION 11-4.24.5 |
| | 3) SHT A-114 DETAILS 1 AND 15 SHOW THE |
| | MEASURMENT FROM THE CENTER OF THE LAVS & |
| | WATER CLOSETS TO THE WALL. FIG 28. 18" |
| | FOR W/C AND 15" FOR LAV. |
| | 4) SHT A-114 HANDICAP SINK AT COUNTER |
| | DETAIL SHALL BE MAXIMUM 34" PER SECTION |
| | 11-4.24.2. DETAIL SHOWS 68" |
| | 5) SHTS A-103 & MP-101 SHOW SECONDARY |
| | ROOF DRAINS IN DIFFERENT LOCATIONS. |
| | CORRELATE PLANS. SECTION 104.2.1 |
| | 6) SHT MP-100 SUBMIT CALCULATIONS FOR |
| | UPPER AND LOWER ROOFS. SHOW SF FOR EACH |
| | AREA AND SHOW 1/2 AREA OF VERTICAL WALLS |
| | INCLUDING PARAPETS ADDED TO CALCULATIONS |
| | FOR EACH AREA. THEN SHOW TOTAL ROOF AREA |
| | DRAINING TO EACH ROOF DRAIN. SECTIONS |
| | 1106, 1107 AND ALL SUBSECTIONS. |
| | 7) SHT P-201 URINAL SHALL CONNECT DOWN- |
| | STREAM OF THE LAV ON THE STACK IN THE |
| | MEN'S TOILET ROOM. SECTION 1104.2.1 |
| | 8) SHT P-201 BREAK ROOM SINK SHALL DIS- |
| | CHARGE DOWNSTREAM OF THE FIXTURES IN THE |
| | WOMENS TOILET ROOM. SECTION 909.1 |
| | 9) SUBMIT STORM RISERS FOR THE PRIMARY |
| | AND SECONDARY ROOF DRAINS, AND SUBMIT |
| | BLDG STORM ISOMETRICS. SHOW ALL PIPE |
| | SIZES AND SLOPE. INDICATE TERMINATION |
| | POINT FOR EACH SYSTEM. |
| | 10) SHT P-201 PLUMBING SPECIFICATIONS, |
| | MATERIALS, (F) AIR CHAMBERS ARE NOT |
| | APPROVED. DELETE FROM REFERENCE. SECTION |
| | 604.9 |
| | |
| | REVIEW BY KEN STEVENS |