| Plan Review Notes For Permit 04051244 |
| Permit Number |
04051244 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-02 00:00:00 | 1) A KNOX-BOX WILL BE REQUIRED. | | | | | | 2) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE FIRE ALARM SYSTEM. FIRE ALARM | | | CIRCUITS SHALL BE CLASS A STYLE D, OR | | | FULLY ADDRESSABLE. | | | | | | 3) THE SITE PLAN DISPLAYS ONLY ONE FIRE | | | HYDRANT. SURELY, THERE ARE OTHER FIRE | | | HYDRANTS IN THE VICINITY. | | | | | | 4) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO, DURING AND AFTER CONSTRUCTION. | | | | | | 5) SUITABLE ROADS ARE TO BE PROVIDED | | | DURING CONSTRUCTION FOR FIRE AND | | | PARAMEDICAL EQUIPMENT. | | | | | | 6) PLEASE INDICATE HOW VEHICLES ARE | | | GOING TO BE DISPLAYED WITHIN THE | | | BUILDING. TYPICALLY,WHEN VEHICLES ARE | | | STORED, THEY CONTAIN VERY LITTLE FUEL | | | HAVE AT LEAST ONE BATTERY TERMINAL | | | DISCONNECTED AND TAPED. ALSO THE GAS CAP | | | IS TO BE LOCKED. | | | | | | 7) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|