| Plan Review Notes For Permit 04051217 |
| Permit Number |
04051217 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-15 00:00:00 | ********* UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE NO INFORMATION WAS | | | SUBMITTED FOR LOAD ON EXSITING MAIN. | | | PLEASE SUBMIT LOAD CALCULATIONS OR | | | COMPLETE FPL READ OUT. | | | NEC 220/215.5 | | | | | | PLEASE SEE ALL OLD/VOIDED SHEETS. NEW | | | SHEETS ARE TO BE INSERTED INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SEE ATTACHED COPY OF FS 553.80(2) | | | (B). THIS IS GIVEN AS A NOTICE TO DESIGN | | | PROFESSIONAL. THIS IS ONLY A NOTICE AT | | | THIS TIME. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|