Plan Review Notes
Plan Review Notes For Permit 04051217
Permit Number 04051217
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHEET 1 SHOW CLEAR FLOOR SPACE FOR
 THE SINK IN ROOM 112. SECTION 11-4.24.5
 AND FOR THE WATER CLOSET AND LAV PER
 SECTIONS 11-4.16.2 & 11-4.19.3.
 2) TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED. ALSO SEE SECTION 410.1
 3) MORE INFORMATION IS REQUIRED FOR THE
 PROCESSOR IN THE DARK ROOM. MANUF.
 SPECIFICATION SHEETS ARE REQUIRED. SECT-
 IONS 104.2.1 & 104.2.1.2 - A DILUTION
 TANK MAY BE REQUIRED IF CHEMICALS ARE
 DISCHARGED IN THE SANITARY SYSTEM. IN
 THAT CASE RODNEY COMPO ENVIRONMENTAL
 COMPLIANCE SHALL BE CONTACTED AT (561)
 837-4074.
 5) BACKFLOW PROTECTION IS REQUIRED FOR
 THE WATER SUPPLY TO THE PROCESSOR. IN-
 DICATE HOW THIS WILL BE ACCOMPLISHED.
 SECTION 608.3
 6) SHT 4 WASH MACHINE REQUIRES A STAND-
 PIPE MINIMUM 2' LONG. SECTIONS 1002.1 &
 802.4. SHOW ON SANT. RISER DIAGRAM.
 CLEANOUT FOR WASH MACHINE SHALL BE
 ACCESSIBLE. MINIMUM OF 4' ABOVE FLOOR.
 SECTION 708.10
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]