| 2004-06-17 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 424.1 SWIMMING POOLS |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) INDICATE WHERE THE DRAIN IS CONNECTED |
| | TO FOR THE SHOWER. SECTION 104.2.1 |
| | 2) PLANS HAVE A TITLE BLOCK OF ARCHITECT |
| | 61G1-16.003 FAC & FS 481.2055 PLANS TO |
| | BE SIGNED, SEALED, AND DATED BY ARCHIT- |
| | ECT OF RECORD. |
| | 3) HEALTH DEPT REQUIREMENTS FOR RESURF- |
| | ACING OF POOLS IS NOTED IN THE ATTACHED |
| | SHEET. THE COUNTY HEALTH DEPT SHALL BE |
| | NOTIFIED IN WRITING OF ANY PROPOSED POOL |
| | RESURFACING OR UPGRADES TO DECKING PRIOR |
| | TO COMMENCEMENT. - THE APPROVAL LETTER |
| | FROM THE HEALTH DEPT. SHALL BE PROVIDED |
| | AT THE TIME OF FIRST INSPECTION OF THE |
| | POOL WORK BY THE CITY OF WPB. |
| | 4) FBC-2001 424.2.12.1 PRESSURE TESTS. |
| | PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| | TEST SHALL BE APPROVED FOR PVC PIPE AND |
| | FITTINGS. (ADD TO NOTES) |
| | 5) FBC-2001 424.2.13.2JOINTS AND CON- |
| | NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| | PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| | NOTES) |
| | 6) SEE BUILDING PLAN REVIEW ON THE SUBJ- |
| | ECT OF THE ADA LIFTS, (DETAIL FOR INST- |
| | ALLATION/ANCHORING - MANUF INSTALLATION |
| | INSTRUCTIONS), FENCE GATE WITH CHILD- |
| | PROOF LATCH DETAIL, FENCE PERMIT ECT. |
| | |
| | REVIEW BY KEN STEVENS |