Plan Review Notes
Plan Review Notes For Permit 04051134
Permit Number 04051134
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-05 00:00:00PLAN REVIEW DENIED FBC 2001 FUEL GAS
 (1) ALL DRAWINGS SHALBEAR THE NAME OF
 THE FIRM AND THE NAME OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 (2) SUBMIT MANUFACTURE SHEETS FOR ALL
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 (3) TOTAL LOAD ON EXISTING SYSTEM AND
 TOTAL DEVELOPED LENGTH TO THE FARTHEST
 OUTLET.
 (4) MANFACTURE INFORMATION FOR PE AND
 PIPE SIZING TABEL.
 END OF COMMENTS, QUESTIONS 561-805-6692