| Plan Review Notes For Permit 04051134 |
| Permit Number |
04051134 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-05 00:00:00 | PLAN REVIEW DENIED FBC 2001 FUEL GAS | | | (1) ALL DRAWINGS SHALBEAR THE NAME OF | | | THE FIRM AND THE NAME OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | (2) SUBMIT MANUFACTURE SHEETS FOR ALL | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | (3) TOTAL LOAD ON EXISTING SYSTEM AND | | | TOTAL DEVELOPED LENGTH TO THE FARTHEST | | | OUTLET. | | | (4) MANFACTURE INFORMATION FOR PE AND | | | PIPE SIZING TABEL. | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|