Plan Review Notes
Plan Review Notes For Permit 04051124
Permit Number 04051124
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-04 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT.
  
 SUBMIT SAME FOR REVIEW PRIOR TO
 INSTALLING ANY GEAR OR CALLING
 INSPECTION ON THE SERVICE.
  
 SUBMIT TWO SETS OF AIC CALCULATIONS AND
 INDICATE COMPLIANCE WITH ARTICLE 110.9
 STATE THE RATING OF THE EQUIPMENT.
 A LETTER AND CALCS SUBMITTED ON A 8 1/2"
 X 11", SIGNED AND SEALED WILL SUFFICE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026