Plan Review Notes
Plan Review Notes For Permit 04051124
Permit Number 04051124
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-17 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM NOT TO CODE.
 SEE RED LINES ON RISER DIAGRAM. W/C'S
 ON 1ST FLOOR ARE NOT VENTED, W/M TO
 DISCHARGE DOWN STREAM OF THE WET VENT
 OF 1/2 BATH. 909.1
 2.DELETE GAS PIPE RISER. GAS CONTRACTOR
 TO SUBMIT PLANS WITH APPLICATION.
 3.W/H PAN REQUIRES A DRAIN TO THE
 OUTSIDE OF BUILDING. 504.8.1 & 2.
 4.THERMAL EXPANSION CONTROL REQUIRED
 PER. 607.3
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH