| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} A TITLE BLOCK IS REQUIRED PER 61G15- |
| | 23.002, PLEASE INCLUDE ALL LICENSE |
| | #'S ON THE REQUIREDBLOCK. |
| | PLEASE ALSO INCLUDE CERTIFICATE OF |
| | AUTHORIZATION #'S WHERE REQUIRED. |
| | |
| | 2} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT PER 110.9. |
| | |
| | 3} THE GROUNDING ELECTRODE CONDUCTOR |
| | MUST BE SIZED PER 250.66 (# 2). |
| | |
| | 4} THE RANGE (OVEN) MUST BE CALCULATED |
| | PER 220.19 (8000 VA., MIN). |
| | |
| | 5} PLEASE LIST ALL THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE PER 210.11(C)(3). |
| | |
| | 6} PROVIDE A RECEPTACLE FOR THE SERVICE |
| | OF THE A/C EQUIPMENT PER 210.63. |
| | |
| | 7} A SMOKE DETECTOR IS REQUIRED IN |
| | PROXIMITY TO THE STAIRS LEADING TO THE |
| | 2ND FLOOR PER 905.2.2 FBC & NFPA-72 |
| | 8-1.4.1.6.2. |
| | |
| | 8} SEE NOTE REFERRING TO200 AMP PANEL |
| | AND LOCATION ARROW, CORRELATE WITH |
| | CORRECT LOCATION. |
| | |
| | 9} THE NOTE REFERRING TO THE AHU-2 |
| | DISCONNECT " ABOVE" IN THE HALL CLOSET |
| | 2ND FLOOR, MUST COMPLY WITH 424-19(A), |
| | "IN SIGHT OF". |
| | |
| | 10} A RECCEPTACLE MUST BE ADDED TO THE |
| | REAR OF THE RESIDENCE TO COMPLY WITH |
| | 210.52(E). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |