 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} A TITLE BLOCK IS REQUIRED PER 61G15-
 23.002, PLEASE INCLUDE ALL LICENSE
 #'S ON THE REQUIREDBLOCK.
 PLEASE ALSO INCLUDE CERTIFICATE OF
 AUTHORIZATION #'S WHERE REQUIRED.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 3} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE SIZED PER 250.66 (# 2).
  
 4} THE RANGE (OVEN) MUST BE CALCULATED
 PER 220.19 (8000 VA., MIN).
  
 5} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE PER 210.11(C)(3).
  
 6} PROVIDE A RECEPTACLE FOR THE SERVICE
 OF THE A/C EQUIPMENT PER 210.63.
  
 7} A SMOKE DETECTOR IS REQUIRED IN
 PROXIMITY TO THE STAIRS LEADING TO THE
 2ND FLOOR PER 905.2.2 FBC & NFPA-72
 8-1.4.1.6.2.
  
 8} SEE NOTE REFERRING TO200 AMP PANEL
 AND LOCATION ARROW, CORRELATE WITH
 CORRECT LOCATION.
  
 9} THE NOTE REFERRING TO THE AHU-2
 DISCONNECT " ABOVE" IN THE HALL CLOSET
 2ND FLOOR, MUST COMPLY WITH 424-19(A),
 "IN SIGHT OF".
  
 10} A RECCEPTACLE MUST BE ADDED TO THE
 REAR OF THE RESIDENCE TO COMPLY WITH
 210.52(E).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  