| 2004-06-28 00:00:00 | DENIED |
| | |
| | 1) SUBMIT A COPY OF THE PAID RECEIPT FOR |
| | THE COUNTY IMPACT FEES. |
| | |
| | 2) SPECIFY THE SIZE OF THE ATTIC ACCESS |
| | ON THE SECOND FLOOR. FBC 2309.6 |
| | |
| | 3) THE FULL BATH ON THE FIRST FLOOR IS |
| | REQUIRED TO HAVE A DOOR WITH A 29" CLEAR |
| | OPENING. FBC 11-4.23.2 |
| | |
| | 4) INCOMPLETE TITLE BLOCK INFORMATION, |
| | FIRM NUMBER, PRINTED NAME OF PERSON |
| | SIGNING AND SEALING, ETC. SEE FS 471 AND |
| | 481. ENGINEER'S TITLE BLOCK INFO IS NOT |
| | ON STRUCTURAL SHEETS. |
| | |
| | 5) INCOMPLETE DESIGN CRITERIA. |
| | FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. NOTE: |
| | INTERNAL PRESSURE COEFFICENT IS + OR - |
| | 0.18 FOR ENCLOSED STRUCTURE IF DESIGNING |
| | TO ASCE 7-98. SPECIFY FBC NOT SBC. |
| | |
| | 6) SPECIFY HOW TERMITE PROTECTION WILL |
| | BE PROVIDED. FBC 1816 |
| | |
| | 7) THE UNVENTED ATTIC WITH ICYNENE |
| | INSULATION IS ACCEPTABLE UNDER FBC 103.7 |
| | ALTERNATE MATERIALS AND METHODS WITH THE |
| | FOLLOWING CONDITIONS. 1) THE SYSTEM/ |
| | ASSEMBLY MUST BE DESIGNED BY A FLORIDA |
| | REGISTERED DESIGN PROFESSIONAL, 2) |
| | INSULATION MUST BE INSTALLED CONTINOUSLY |
| | IN THE UPPER PLANE OF THE ROOF ASSEMBLY |
| | DECK/SHEATHING WITH SPECIFIED, APPROVED |
| | INSULATION PRODUCTS, AND THE CEILING |
| | SPACE IS NOT SEPARATED FROM THE |
| | CONDITIONED SPACE BELOW WITH INSULATION. |
| | SUBMIT SIGNED AND SEALED REPORT SPECIFY- |
| | ING HOW MATERIAL IS TO BE APPLIED AND |
| | MATERIAL SPECIFICATIONS. |
| | |
| | 8) THE BALCONY GUARDRAIL IS REQUIRED TO |
| | HAVE A BOTTOM RAIL THAT WILL REJECT A |
| | 2" DIAMETER SPHERE. FBC 1015.3 |
| | |
| | 9) SPECIFY THE CONNECTORS THAT WILL BE |
| | USED TO ATTACH THE 2ND FLOOR POST |
| | COLUMNS TO THE WOOD BEAMS. |
| | |
| | 10) SPECIFY THE ATTACHMENT OF THE 2ND |
| | FLOOR GUARDRAILS TO THE WOOD COLUMNS. |
| | |
| | 11) INDICATE ON THE PLANS THAT THE SPACE |
| | BETWEEN THE INTERMEDIATE RAILS AT THE |
| | INTERIOR STAIRS WILL REJECT A 4" SPHERE. |
| | SEE FBC 1015.3 |
| | |
| | 12) PROVIDE DETAILS, SECTIONS, ETC. |
| | INDICATING THE CONSTRUCTION AND |
| | CONNECTIONS OF THE TWO CHIMNEYS. SPECIFY |
| | THE REQUIRED HEIGHT ABOVE THE ROOF PER |
| | FBC 2804.2.4. |
| | |
| | 13) SPECIFY RING SHANK NAILS FOR ROOF |
| | SHEATHING IN ZONE 3 FOR MEAN ROOF HEIGHT |
| | OF 25'- 35' PER CITY AMENDMENTS TO FBC |
| | TABLE 2306.1. |
| | |
| | 14) SPECIFY A BOTTOM CORD LIVE LOAD OF |
| | 10 PSF FOR ATTICS WITHOUT STORAGE. SEE |
| | FBC TABLE 1604.1 |
| | |
| | 15) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | SUBMIT STATE PRODUCT APPROVAL FOR THE |
| | FOLLOWING: |
| | - TRUSS CONNECTORS |
| | - DOUBLE HUNG WINDOWS (IMPACT) |
| | - OVERHEAD GARAGE DOORS |
| | - FIXED WINDOWS (IMPACT) |
| | - 8-PANEL DOOR TO LAWN STORAGE |
| | NOTE: PRODUCT APPROVALS MUST BE APPROVED |
| | BY THE HISTORIC PRESERVATION DEPT. |
| | THE STOREFRONT DOORS MAY NOT BE ACCEPT- |
| | ABLE. |
| | NO CASEMENT WINDOWS ARE SHOWN ON PLANS. |
| | WHY WAS PRODUCT APPROVAL FOR CASEMENT |
| | WINDOWS SUBMITTED. |
| | |
| | 16) THE UPLIFT VALUE FOR THE HETAL 20 |
| | CONNECTOR IN THE ANCHOR SCHEDULE IS |
| | INCORRECT. THE UPLIFT VALUE IS 1810# |
| | WITHOUT THE ONE THIRD STRESS INCREASE IN |
| | THE STEEL CALCULATIONS. SEE 2004 SIMPSON |
| | CATALOG. |
| | |