Plan Review Notes
Plan Review Notes For Permit 04051124
Permit Number 04051124
Review Stop B
Sequence Number 1
Notes
Date Text
2004-06-28 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR
 THE COUNTY IMPACT FEES.
  
 2) SPECIFY THE SIZE OF THE ATTIC ACCESS
 ON THE SECOND FLOOR. FBC 2309.6
  
 3) THE FULL BATH ON THE FIRST FLOOR IS
 REQUIRED TO HAVE A DOOR WITH A 29" CLEAR
 OPENING. FBC 11-4.23.2
  
 4) INCOMPLETE TITLE BLOCK INFORMATION,
 FIRM NUMBER, PRINTED NAME OF PERSON
 SIGNING AND SEALING, ETC. SEE FS 471 AND
 481. ENGINEER'S TITLE BLOCK INFO IS NOT
 ON STRUCTURAL SHEETS.
  
 5) INCOMPLETE DESIGN CRITERIA.
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF. NOTE:
 INTERNAL PRESSURE COEFFICENT IS + OR -
 0.18 FOR ENCLOSED STRUCTURE IF DESIGNING
 TO ASCE 7-98. SPECIFY FBC NOT SBC.
  
 6) SPECIFY HOW TERMITE PROTECTION WILL
 BE PROVIDED. FBC 1816
  
 7) THE UNVENTED ATTIC WITH ICYNENE
 INSULATION IS ACCEPTABLE UNDER FBC 103.7
 ALTERNATE MATERIALS AND METHODS WITH THE
 FOLLOWING CONDITIONS. 1) THE SYSTEM/
 ASSEMBLY MUST BE DESIGNED BY A FLORIDA
 REGISTERED DESIGN PROFESSIONAL, 2)
 INSULATION MUST BE INSTALLED CONTINOUSLY
 IN THE UPPER PLANE OF THE ROOF ASSEMBLY
 DECK/SHEATHING WITH SPECIFIED, APPROVED
 INSULATION PRODUCTS, AND THE CEILING
 SPACE IS NOT SEPARATED FROM THE
 CONDITIONED SPACE BELOW WITH INSULATION.
 SUBMIT SIGNED AND SEALED REPORT SPECIFY-
 ING HOW MATERIAL IS TO BE APPLIED AND
 MATERIAL SPECIFICATIONS.
  
 8) THE BALCONY GUARDRAIL IS REQUIRED TO
 HAVE A BOTTOM RAIL THAT WILL REJECT A
 2" DIAMETER SPHERE. FBC 1015.3
  
 9) SPECIFY THE CONNECTORS THAT WILL BE
 USED TO ATTACH THE 2ND FLOOR POST
 COLUMNS TO THE WOOD BEAMS.
  
 10) SPECIFY THE ATTACHMENT OF THE 2ND
 FLOOR GUARDRAILS TO THE WOOD COLUMNS.
  
 11) INDICATE ON THE PLANS THAT THE SPACE
 BETWEEN THE INTERMEDIATE RAILS AT THE
 INTERIOR STAIRS WILL REJECT A 4" SPHERE.
 SEE FBC 1015.3
  
 12) PROVIDE DETAILS, SECTIONS, ETC.
 INDICATING THE CONSTRUCTION AND
 CONNECTIONS OF THE TWO CHIMNEYS. SPECIFY
 THE REQUIRED HEIGHT ABOVE THE ROOF PER
 FBC 2804.2.4.
  
 13) SPECIFY RING SHANK NAILS FOR ROOF
 SHEATHING IN ZONE 3 FOR MEAN ROOF HEIGHT
 OF 25'- 35' PER CITY AMENDMENTS TO FBC
 TABLE 2306.1.
  
 14) SPECIFY A BOTTOM CORD LIVE LOAD OF
 10 PSF FOR ATTICS WITHOUT STORAGE. SEE
 FBC TABLE 1604.1
  
 15) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT STATE PRODUCT APPROVAL FOR THE
 FOLLOWING:
 - TRUSS CONNECTORS
 - DOUBLE HUNG WINDOWS (IMPACT)
 - OVERHEAD GARAGE DOORS
 - FIXED WINDOWS (IMPACT)
 - 8-PANEL DOOR TO LAWN STORAGE
 NOTE: PRODUCT APPROVALS MUST BE APPROVED
 BY THE HISTORIC PRESERVATION DEPT.
 THE STOREFRONT DOORS MAY NOT BE ACCEPT-
 ABLE.
 NO CASEMENT WINDOWS ARE SHOWN ON PLANS.
 WHY WAS PRODUCT APPROVAL FOR CASEMENT
 WINDOWS SUBMITTED.
  
 16) THE UPLIFT VALUE FOR THE HETAL 20
 CONNECTOR IN THE ANCHOR SCHEDULE IS
 INCORRECT. THE UPLIFT VALUE IS 1810#
 WITHOUT THE ONE THIRD STRESS INCREASE IN
 THE STEEL CALCULATIONS. SEE 2004 SIMPSON
 CATALOG.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714