| Plan Review Notes For Permit 04051102 |
| Permit Number |
04051102 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-26 00:00:00 | 1) DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) PLEASE PROVIDE PRESCRIPTIVE | | | STRENGTH REQUIREMENTS FOR NEW HANDRAILS | | | AND GUARDRAILS. | | | | | | 3) STAIRS SHALL BE NO LESS THAN 4 INCHES | | | NO GREATER THAN 7 INCHES AND TREADS | | | SHALL BE NO LESS THAN 11 INCHES. | | | | | | 4) PLEASE DEMONSTRATE THAT SPHERES OF | | | VARIOUS SIZES WILL NOT PASS THROUGH | | | HANDRAILS AND GUARDRAILS. | | | | | | 5) PLEASE INDICATE HOW REMOVAL OF | | | STAIRS WILL IMPACT THE REST OF THE | | | PARKING GARAGE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|