Plan Review Notes
Plan Review Notes For Permit 04051074
Permit Number 04051074
Review Stop B
Sequence Number 1
Notes
Date Text
2004-05-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) 61G15-23.002(2)FL. ADMIN. CODE.
 THE PLANS DO NOT INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER OF BROMLEY-COOK
 ENGINEERING, INC.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 ADD THE CERTIFICATE OF AUTHORIZATION #.
 (471.025 F.S. AND 471.023 F.S.).
  
 2) 61G15-23.002(1)FL. ADMIN. CODE.
 THE PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME ON EACH SHEET.THE 'SIGNATURE' ON
 THE SUBMITTED SHEETS IS MARGINALLY MORE
 COMPLEX THAN A CHECK MARK AND VARIES
 SIGNIFICANTLY FROM SHEET TO SHEET.WE
 HAVE RECENTLY CONTACTED THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS ABOUT
 SIMILAR CASES AND THEY HAVE ADVISED THAT
 A PROFESSIONAL ENGINEER'S SIGNATURES
 SHOULD INCORPORATE A LEGIBLE FIRST AND
 LAST NAME.WILLIAM COOK, P.E. SHALL
 RE-SIGN EACH SHEET OR SUBMIT A NOTARIZED
 SIGNED/SEALED LETTER STATING THAT THE
 SIGNATURE ON THE LETTER IS THE SAME AS
 THAT HELD ON FILE BY THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS.THAT LETTER
 WILL BE SUBMITTED TO THE BOARD FOR
 VERIFICATION.(471.025 F.S.).
  
 3) FBC* 105.13.1THRESHOLD BUILDING.
 ONLY TWO COPIES OF THE PLANS WERE
 SUBMITTED.SUBMIT THREE COPIES OF THE
 PLANS AND OTHER DOCUMENTS REQUIRED FOR
 PERMITTING PURPOSES.
  
 4) FIXED WINDOW SERIES FX345.THE
 MIAMI-DADE PRODUCT APPROVAL NOTICE OF
 ACCEPTANCE #03-1023.02 IS PENDING
 APPROVAL.SUBMITTAL OF THE FENESTRATION
 TESTING LABORATORY TEST REPORT IS NOTED.
 DUE TO THE LACK OF A PRODUCT APPROVAL
 FORM MIAMI-DADE OR SBCCI, LOCAL PRODUCT
 APPROVAL IS REQUIRED.THE REQUIRED FORM
 IS ATTACHED TO THESE COMMENTS AND SHOULD
 BE COMPLETED, SIGNED AND SEALED BY A
 STATE OF FLORIDA, PROFESSIONAL ENGINEER
 (SECTIONS 1.0-9.0) WITH THE FENESTRATION
 TESTING LABORATORY REPORT SUBMITTED AS
 SUPPORTING DOCUMENTATION.THE FORM
 SHALL BE ACKNOWLEDGED BY THE ARCHITECT
 OF RECORD FOR THE BUILDING (SECTION 10).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]