2004-06-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04051056
 ADD: 3308 45TH ST
 CONT: STEVE THOMSON
 TEL: (561)248-9594
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) ALL SUBMITTALS, GEOTECH REPORT, PRO-
 DUCT APPROVALS REQUIRE (2) TWO COPIES
 FOR EACH PERMIT. PHASE I AND PHASEII ARE
 STAND ALONE PERMITS!
  
 2) THIS WAS COMMENT # 8 FROM 1ST REVIEW
 DISCREPANCY FLOOR PLAN AND ELEVATIONS
 THE FLOOR PLAN DOES NOT MATCH THE ELE-
 VATIONS. ELEVATIONS FOR EAST AND WEST
 ARE REVERSED.
  
 3) PART "B" OF COMMENT 8 1ST REVIEW,
 THE LOUVERS ARE ON THE WEST ELEVATION
 LESS THAN 15'-0" FROM THE PROIPERTY LINE
 REQUIRING A 45 MIN RATING, THE MANUFAC-
 TURES SPEC SHEET SUBMITTED ARE FOR (2)
 SEPERATE SYSTEMS, NOT A TESTED ASSEMBLY.
 THE RUSKIN IS NOT LISTED ON THE FLORIDA
 STATEWIDE PRODUCT APPROVAL SYSTEM.
  
 4)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) COMMENT # 16 FROM 1ST REVIEW,
 PROVIDE INFORMATION AS WHAT WILL BE
 FABRICATED, SINCE FACTORY OCC, WHAT TYPE
 OF FUTURE EQUIPMENT WILL BE USED?
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW