Plan Review Notes
Plan Review Notes For Permit 04051044
Permit Number 04051044
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-28 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 2} AN EQUIPMENT GROUND MUST BE RAN TO
 THE PANEL FROM THE DISCONNECT PER
 250.122.
  
 3} PLEASE INDICATE SERVICE EQUIPMENT
 LOCATION ON THE PLAN.
  
 4} PLEASE SEE MISSING RECEPTACLES FOR
 FRONT AND/OR REAR OF DWELLING.210.52(E).
  
 5} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 6} SMOKE DETECTORS ARE REQUIRE BY
 ARTICLE 8-1.4.1.6.2 NFPA-72, PLACE SAME
 ON DRAWINGS FOR REVIEW.
  
 7} THE KITCHEN NEEDS A RECEPTACLE TO
 COMPLY WITH 210.52(C).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026