| Notes |
| Date |
Text |
| 2004-05-28 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING | | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | | CURRENT PER 110.9. | | | | | | 2} AN EQUIPMENT GROUND MUST BE RAN TO | | | THE PANEL FROM THE DISCONNECT PER | | | 250.122. | | | | | | 3} PLEASE INDICATE SERVICE EQUIPMENT | | | LOCATION ON THE PLAN. | | | | | | 4} PLEASE SEE MISSING RECEPTACLES FOR | | | FRONT AND/OR REAR OF DWELLING.210.52(E). | | | | | | 5} PLEASE LIST THE REQUIRED ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | | | 6} SMOKE DETECTORS ARE REQUIRE BY | | | ARTICLE 8-1.4.1.6.2 NFPA-72, PLACE SAME | | | ON DRAWINGS FOR REVIEW. | | | | | | 7} THE KITCHEN NEEDS A RECEPTACLE TO | | | COMPLY WITH 210.52(C). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|