| Plan Review Notes For Permit 04051041 |
| Permit Number |
04051041 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-02 00:00:00 | ************* UNSAT ************** | | | | | | 1 )NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SHOW PER | | | 220.3,220.10,220.11,220.13 ETC. | | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | | AT 125% PER 215.3,230.42 | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS CORRELATE WITH THE SUBMITTED PANEL | | | SCHEDULE. PLEASE CIRCUIT EM/EXT LTS | | | PER 700.12E. | | | | | | 3)NOTE: PLEASE SEE PLANS SHOW TWO NEW | | | PANELS, YET RISER INDICATE ONLY ONE. | | | RISER INDICATES A NEW 200A DISC, IS THIS | | | THE 200A PANEL? | | | | | | 4)NOTE: PLEASE METHOD OF EQUIPMENT | | | GRONDING BETWEEN MAIN DISC AND PANEL. | | | 250.110/250.24 PER 250.122 | | | | | | 5)NOTE: PLEASE SEE RISER AND ELEC RM | | | LAYOUT. LAYOUT SHOWS MANY MORE PANELS | | | THAN ON RISER? | | | PLEASE SHOW SIZE OF EXISTING SERVICE | | | AND SERVICE ENT CONDUCTORS.215.5 | | | | | | 6)NOTE: PLEASE SEE FS 481.221 WHICH ALSO | | | REQ'S ARCH TO DATE PLANS WHEN SIGNED AND | | | SEALED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|