2005-04-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHTS P-2.1 & P2.6 WATER CLOSET NOT
 VENTED. RISER SHALL CONNECT DOWNSTREAM
 OF THE VENTED LINE. SEE RISER "V"
 2) SHT P-2.1 & P2.6 MORE INFORMATION IS
 REQUIRED FOR THE SPA. MANUF INFORMATION
 IS REQUIRED TO SEE HOW THE DRAIN FOR THE
 SPA WILL BE PIPED TO THE HUB DRAIN.
 SECTION 104.2.1.
 3) SHT P-2.1 GREASE TRAP IN THE PANTRY
 IS NOT APPROVED. PLEASE CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE FOR THE
 GREASE TRAP REQUIREMENTS. (561) 805 2272
 OR E-MAIL [email protected]. WASTE ORD.
 #2938-96.
 4) IF FOOD IS BEING PREPARED ON SITE FOR
 PUBLIC CONSUMPTION THE HEALTH DEPT WILL
 BE REQUIRED TO BE NOTIFIED. NOTIFY THE
 PALM BEACH COUNTY HEALTH UNIT, DIVISION
 OF ENVIRONMENTAL HEALTH. (561) 355-3018.
 PLEASE CLARIFY. - ALSO IF FOOD IS BEING
 PREPARED, THE SINKS IN THE FOOD PREP
 AREA SHALL BE INDIRECT WASTED PER
 SECTION 802.1.1.
 5) SHT P-2.1 SK3 SINK IS NOT SHOWN ON
 THE FLOOR PLAN. THE SANITARY PIPING IS
 SHOWN FOR THIS SINK IN THE PANTRY AREA.
 6) SHT P-2.1 RAIN WATER LEADER (9) IS
 POINTING TO THE SANT. RISER AT
 REGISTRATION AREA. SECTION 104.2.1.
 7) SHT P-2.1 ISOMETRIC SANT. RISER
 DIAGRAMS ARE REQUIRED FOR THE PIPING TO
 THE EXERCISE ROOM/SPA, FLOOR DRAIN,
 DRINKING FOUNTAIN, PANTRY AREA, AND THE
 EMPLOYEE AREA. SECTION 104.3.1.1.
 8) SHTS P-2.1, & P-2.2 AND ASSOCIATED
 RISER DIAGRAMS, ALL SAFEWASTES ARE NOT
 APPROVED. SEE SPA DRAIN, FLOOR DRAIN
 FROM TRENCH DRAIN, & FLOOR DRAIN IN THE
 EMPLOYEE AREA UPSTREAM OF THE MOP SINK.
 ALL FLOOR DRAINS SHALL HAVE A SEPARATE
 TRAP AND CONNECT AT THE VENTED LINE
 SEPARATELY.
 9) SHT P-2.1 6" REQUIRED ON THE BUILDING
 DRAIN DOWNSTREAM OF THE "W" RISER
 DIAGRAM. SHOWS 175 DFU BUT RECHECKING
 THE FIGURES, THEY ADD UP TO 183 DFU.
 10) SHTS P-2.1, P-2.2, P-2.5, & P-2.6
 CHECK ALL ADDITION OF FIXTURE UNITS ON
 THE RISERS AND THE ACCUMULATED FIXTURE
 UNITS IN THE BUILDING SANT. DRAIN. THERE
 IS A DISCREPANCY IN THE NUMBERS. SECTION
 104.2.1.
 11) SHTS P-2.2 & P-2.5 W/C NOT VENTED
 AND HORIZONTAL DRY VENT NOT APPROVED.
 SEE RISER D&E. SECTIONS 901.2.1, 905.3,
 AND 905.4
 12) SHTS P-2.1 & P-2.2 VENT NOT SHOWN ON
 THE LINE DOWNSTREAM OF THE 4" TRENCH
 DRAIN. SECTION 104.2.1.
 13) SHT P-2.5 SANT. RISER "X" DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS. NO HUB DRAINS ARE
 SHOWN ON THE FLOOR PLAN FOR THE SECOND
 AND THIRD FLOORS. SANT. DRAIN LINE SHALL
 NOT BE REDUCED IN THE DIRECTION OF FLOW.
 SECTION 704.2. SEE TUB/SHR RISER
 SECTION.
 14) SHT P-2.5 SANT. RISER "Q" DOES NOT
 REFLECT THE FLOOR PLAN. NO WASH MACHINE
 IS SHOWN ON THE 2ND FLOOR OF THE FLOOR
 PLAN. SECTION 104.2.1.
 15) SHT P-2.6 SANT. RISER "M" DOES NOT
 REFLECT THE FLOOR PLAN. THE TUB/SHR AND
 SK-2 LAYOUT ON THE RISER DOES NOT
 REFLECT THE FLOOR PLAN LAYOUT. SECTION
 104.2.1.
 16) SHT P-2.7 RECHECK ALL DRAINAGE
 FIXTURE UNITS AND PIPE SIZE. ALSO GREASE
 INTERCEPTOR NOT APPROVED.
 17) SHT P-5.1 TYPICAL RAIN WATER
 ISOMETRIC DOES NOT REFLECT ALL RISER
 DIAGRAMS. PLEASE SUBMIT RISERS FOR EACH
 TYPE OF RWL. SECTION 104.3.1.1.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 PLEASE RETURN THE RED LINE COPY OF THE
 REVISION TO HELP EXPEDITE REVISION.
  