Date |
Text |
2005-04-13 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| |
| 1) SHTS P-2.1 & P2.6 WATER CLOSET NOT |
| VENTED. RISER SHALL CONNECT DOWNSTREAM |
| OF THE VENTED LINE. SEE RISER "V" |
| 2) SHT P-2.1 & P2.6 MORE INFORMATION IS |
| REQUIRED FOR THE SPA. MANUF INFORMATION |
| IS REQUIRED TO SEE HOW THE DRAIN FOR THE |
| SPA WILL BE PIPED TO THE HUB DRAIN. |
| SECTION 104.2.1. |
| 3) SHT P-2.1 GREASE TRAP IN THE PANTRY |
| IS NOT APPROVED. PLEASE CONTACT RODNEY |
| COMPO, ENVIRONMENTAL COMPLIANCE FOR THE |
| GREASE TRAP REQUIREMENTS. (561) 805 2272 |
| OR E-MAIL [email protected]. WASTE ORD. |
| #2938-96. |
| 4) IF FOOD IS BEING PREPARED ON SITE FOR |
| PUBLIC CONSUMPTION THE HEALTH DEPT WILL |
| BE REQUIRED TO BE NOTIFIED. NOTIFY THE |
| PALM BEACH COUNTY HEALTH UNIT, DIVISION |
| OF ENVIRONMENTAL HEALTH. (561) 355-3018. |
| PLEASE CLARIFY. - ALSO IF FOOD IS BEING |
| PREPARED, THE SINKS IN THE FOOD PREP |
| AREA SHALL BE INDIRECT WASTED PER |
| SECTION 802.1.1. |
| 5) SHT P-2.1 SK3 SINK IS NOT SHOWN ON |
| THE FLOOR PLAN. THE SANITARY PIPING IS |
| SHOWN FOR THIS SINK IN THE PANTRY AREA. |
| 6) SHT P-2.1 RAIN WATER LEADER (9) IS |
| POINTING TO THE SANT. RISER AT |
| REGISTRATION AREA. SECTION 104.2.1. |
| 7) SHT P-2.1 ISOMETRIC SANT. RISER |
| DIAGRAMS ARE REQUIRED FOR THE PIPING TO |
| THE EXERCISE ROOM/SPA, FLOOR DRAIN, |
| DRINKING FOUNTAIN, PANTRY AREA, AND THE |
| EMPLOYEE AREA. SECTION 104.3.1.1. |
| 8) SHTS P-2.1, & P-2.2 AND ASSOCIATED |
| RISER DIAGRAMS, ALL SAFEWASTES ARE NOT |
| APPROVED. SEE SPA DRAIN, FLOOR DRAIN |
| FROM TRENCH DRAIN, & FLOOR DRAIN IN THE |
| EMPLOYEE AREA UPSTREAM OF THE MOP SINK. |
| ALL FLOOR DRAINS SHALL HAVE A SEPARATE |
| TRAP AND CONNECT AT THE VENTED LINE |
| SEPARATELY. |
| 9) SHT P-2.1 6" REQUIRED ON THE BUILDING |
| DRAIN DOWNSTREAM OF THE "W" RISER |
| DIAGRAM. SHOWS 175 DFU BUT RECHECKING |
| THE FIGURES, THEY ADD UP TO 183 DFU. |
| 10) SHTS P-2.1, P-2.2, P-2.5, & P-2.6 |
| CHECK ALL ADDITION OF FIXTURE UNITS ON |
| THE RISERS AND THE ACCUMULATED FIXTURE |
| UNITS IN THE BUILDING SANT. DRAIN. THERE |
| IS A DISCREPANCY IN THE NUMBERS. SECTION |
| 104.2.1. |
| 11) SHTS P-2.2 & P-2.5 W/C NOT VENTED |
| AND HORIZONTAL DRY VENT NOT APPROVED. |
| SEE RISER D&E. SECTIONS 901.2.1, 905.3, |
| AND 905.4 |
| 12) SHTS P-2.1 & P-2.2 VENT NOT SHOWN ON |
| THE LINE DOWNSTREAM OF THE 4" TRENCH |
| DRAIN. SECTION 104.2.1. |
| 13) SHT P-2.5 SANT. RISER "X" DOES NOT |
| REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| CODE REQUIREMENTS. NO HUB DRAINS ARE |
| SHOWN ON THE FLOOR PLAN FOR THE SECOND |
| AND THIRD FLOORS. SANT. DRAIN LINE SHALL |
| NOT BE REDUCED IN THE DIRECTION OF FLOW. |
| SECTION 704.2. SEE TUB/SHR RISER |
| SECTION. |
| 14) SHT P-2.5 SANT. RISER "Q" DOES NOT |
| REFLECT THE FLOOR PLAN. NO WASH MACHINE |
| IS SHOWN ON THE 2ND FLOOR OF THE FLOOR |
| PLAN. SECTION 104.2.1. |
| 15) SHT P-2.6 SANT. RISER "M" DOES NOT |
| REFLECT THE FLOOR PLAN. THE TUB/SHR AND |
| SK-2 LAYOUT ON THE RISER DOES NOT |
| REFLECT THE FLOOR PLAN LAYOUT. SECTION |
| 104.2.1. |
| 16) SHT P-2.7 RECHECK ALL DRAINAGE |
| FIXTURE UNITS AND PIPE SIZE. ALSO GREASE |
| INTERCEPTOR NOT APPROVED. |
| 17) SHT P-5.1 TYPICAL RAIN WATER |
| ISOMETRIC DOES NOT REFLECT ALL RISER |
| DIAGRAMS. PLEASE SUBMIT RISERS FOR EACH |
| TYPE OF RWL. SECTION 104.3.1.1. |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. - |
| PLEASE RETURN THE RED LINE COPY OF THE |
| REVISION TO HELP EXPEDITE REVISION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |