Plan Review Notes
Plan Review Notes For Permit 04051040
Permit Number 04051040
Review Stop P
Sequence Number 2
Notes
Date Text
2004-08-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 5) ALL ARCHITECTURAL SHEETS SHALL SHOW
 THE PRINTED NAME OF THE PERSON RESPONSI-
 BLE FOR SEALING THE DOCUMENT. FAC 61G1-
 16.004(6) & FS 481.2055. - SHEETS A-1.1C
 AND A-3.1A PRINTED NAME MISSING.
 FROM PREVIOUS REVIEW:
 6) SHT A-4.1 ROLL IN SHOWER DETAIL, SHOW
 DETAIL FOR SEAT 11-4.21.3, GRAB BARS 11-
 4.21.4, CONTROLS 11-4.21.5, & SHOWER
 UNIT 11-4.21.6. - ALSO SEE FIGURES 37B,
 57A AND 57B.
 FROM PREVIOUS REVIEW:
 22) SHTS P-2.5 & P-2.6 MANY RISERS DO
 NOT REFLECT THE FLOOR PLANS. CORRELATE
 THE RISERS AND FLOOR PLANS. SEC 104.2.1.
 D) 1 WATER CLOSET ON FLOOR PLAN BUT 2
 SHOWN ON RISER.
 H) P2.4 STATES 2ND FLOOR ONLY, BUT RIS-
 ER AND FLOOR PLAN SHOWS 2ND AND THIRD
 FLOOR.
 M) FLOOR DRAIN NOT VENTED. SEC 901.2.1
 AND 907.1 - NO OFFSETS ALLOWED ON WASTE
 STACK SECTION 910.2
 Q) WASH MACHINE REQUIRES A STANDPIPE
 SECTIONS 1002.1 & 802.4, AND A CLEANOUT
 4' ABOVE THE FLOOR SECTION 708.10.
 Z) FLOOR DRAIN IS NOT VENTED. SECTIONS
 901.2.1 & 907.1
 FROM PREVIOUS REVIEW:
 31) FOLLOWING INFORMATION REQUIRED FOR
 GAS APPROVAL/PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - NOT ALL PIPE SIZE AND
 LENGTHS OF PIPE ARE SHOWN. MINIMUM 1-1/2
 INCH PIPE REQUIRED FROM THE METER TO THE
 1-1/4X1-1/4X1-1/2 INCH TEE. MIN. 1-1/4"
 REQUIRED TO THE FIRST HEATER WITH 1" RE-
 QUIRED TO THE OTHER 2 HEATERS ON 1/2 LB
 SYSTEM MAXIMUM 20'. (THIS DISTANCE IS
 NOT SHOWN ON RISER DIAGRAM). DOES EACH
 DRYER AND SINGLE WATER HEATER HAVE A 2
 LB. TO 1/2 LB. REGULATOR? INDICATE ON
 RISER DIAGRAM. SHOW ALL LENGTHS OF PIPE
 AND PIPE SIZES. INDICATE WHERE PRESSURE
 CHANGES.
 NEW COMMENT:
 1B) SEE ATTACHED SHEET CONCERNING FS
 553.80(2)(B) DESIGN PROFESSIONAL DOCU-
 MENTS.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]