Date |
Text |
2004-08-09 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FBC-2001 BUILDING |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| FROM PREVIOUS REVIEW: |
| 5) ALL ARCHITECTURAL SHEETS SHALL SHOW |
| THE PRINTED NAME OF THE PERSON RESPONSI- |
| BLE FOR SEALING THE DOCUMENT. FAC 61G1- |
| 16.004(6) & FS 481.2055. - SHEETS A-1.1C |
| AND A-3.1A PRINTED NAME MISSING. |
| FROM PREVIOUS REVIEW: |
| 6) SHT A-4.1 ROLL IN SHOWER DETAIL, SHOW |
| DETAIL FOR SEAT 11-4.21.3, GRAB BARS 11- |
| 4.21.4, CONTROLS 11-4.21.5, & SHOWER |
| UNIT 11-4.21.6. - ALSO SEE FIGURES 37B, |
| 57A AND 57B. |
| FROM PREVIOUS REVIEW: |
| 22) SHTS P-2.5 & P-2.6 MANY RISERS DO |
| NOT REFLECT THE FLOOR PLANS. CORRELATE |
| THE RISERS AND FLOOR PLANS. SEC 104.2.1. |
| D) 1 WATER CLOSET ON FLOOR PLAN BUT 2 |
| SHOWN ON RISER. |
| H) P2.4 STATES 2ND FLOOR ONLY, BUT RIS- |
| ER AND FLOOR PLAN SHOWS 2ND AND THIRD |
| FLOOR. |
| M) FLOOR DRAIN NOT VENTED. SEC 901.2.1 |
| AND 907.1 - NO OFFSETS ALLOWED ON WASTE |
| STACK SECTION 910.2 |
| Q) WASH MACHINE REQUIRES A STANDPIPE |
| SECTIONS 1002.1 & 802.4, AND A CLEANOUT |
| 4' ABOVE THE FLOOR SECTION 708.10. |
| Z) FLOOR DRAIN IS NOT VENTED. SECTIONS |
| 901.2.1 & 907.1 |
| FROM PREVIOUS REVIEW: |
| 31) FOLLOWING INFORMATION REQUIRED FOR |
| GAS APPROVAL/PERMIT. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. - NOT ALL PIPE SIZE AND |
| LENGTHS OF PIPE ARE SHOWN. MINIMUM 1-1/2 |
| INCH PIPE REQUIRED FROM THE METER TO THE |
| 1-1/4X1-1/4X1-1/2 INCH TEE. MIN. 1-1/4" |
| REQUIRED TO THE FIRST HEATER WITH 1" RE- |
| QUIRED TO THE OTHER 2 HEATERS ON 1/2 LB |
| SYSTEM MAXIMUM 20'. (THIS DISTANCE IS |
| NOT SHOWN ON RISER DIAGRAM). DOES EACH |
| DRYER AND SINGLE WATER HEATER HAVE A 2 |
| LB. TO 1/2 LB. REGULATOR? INDICATE ON |
| RISER DIAGRAM. SHOW ALL LENGTHS OF PIPE |
| AND PIPE SIZES. INDICATE WHERE PRESSURE |
| CHANGES. |
| NEW COMMENT: |
| 1B) SEE ATTACHED SHEET CONCERNING FS |
| 553.80(2)(B) DESIGN PROFESSIONAL DOCU- |
| MENTS. |
| *********WHEN RESUBMITTING PLANS******** |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |