2004-06-17 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 BUILDING |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) SHT SP-1 RPZ BACKFLOW IS REQUIRED ON |
| THE WATER SERVICE. PLAN SHOWS A BACKWAT- |
| ER VALVE. SECTIONS 608.13.2 & 104.2.1. |
| 2) SHT SP-1 MORE INFORMATION REQUIRED ON |
| THE ENTRANCE FOUNTAIN. WILL THERE BE A |
| DRAIN AND OR WATER SUPPLY TO THE FOUNT- |
| AIN? IF SO SHOW PIPING AND TERMINATION |
| OF DRAIN AND THE WATER SUPPLY SHALL BE |
| EQUIPPED WITH AN RPZ BACKFLOW. SECTION |
| 104.2.1. |
| 3) SHT A-1.1 THE FOLLOWING TOILET ROOMS |
| SHALL BE ACCESSIBLE AND SHALL CONFORM TO |
| SECTION 11-4.22. THE WORKSHOP/MAINT., |
| TOILET ROOMS AT LANUDRY ROOM, MENS AND |
| WOMENS TOILET ROOMS NEAR THE EXERCISE |
| ROOM. SUBMIT A DETAIL SHOWING COMPLIANCE |
| WITH SECTIONS 11-4.16, 11-4.19, AND |
| 11-4.22 AND ALL SUBSECTIONS. |
| 4) SHT A-1.1 SINKS IN EMPLOYEE AREA ARE |
| TO BE ACCESSIBLE. SUBMIT A DETAIL TO |
| SHOW COMPLIANCE WITH 11-4.24 AND ALL |
| SUBSECTIONS. |
| 5) ALL ARCHITECTURAL SHEETS SHALL SHOW |
| THE PRINTED NAME OF THE PERSON RESPONSI- |
| BLE FOR SEALING THE DOCUMENT. FAC |
| 61G1-16.004(6) & FS 481.2055. |
| 6) SHT A-4.1 ROLL IN SHOWER DETAIL SHOW |
| DETAIL FOR SEAT 11-4.21.3, GRAB BARS 11- |
| 4.21.4, CONTROLS 11-4.21.5, SHOWER UNIT |
| 11-4.21.6. |
| 7) SHT A-4.2 SHOW A DETAIL FOR THE KING |
| JAC SUITE THAT IS TO BE ACCESSIBLE. |
| SECTION 104.2.1. |
| 8) SHT A-4.2 HDCP DETAILS, WATER CLOSET |
| SHALL NOT BE IN THE TURNING AREA. THE |
| AREA SHALL BE UNOBSTRUCTED PER SECTIONS |
| 11-4.2.3 & 11-4.22.3. |
| 9) SHT A-5 ROOF PLAN, SHOW GUTTER SIZE |
| FOR LOWER FLAT ROOF. SHOW LOCATION OF |
| DOWNSPOUTS. PLAN INDICATES THAT THE GUT- |
| TER IS ON ALL SIDES OF ROOF. SHOW SQUARE |
| FOOTAGE OF ROOF AND SHOW 1/2 AREA OF ALL |
| VERTICAL WALLS ADDED TO AREA OF ROOF FOR |
| SIZING GUTTERS AND DOWNSPOUTS PER SECT- |
| IONS 1106 & 1107 AND ALL SUBSECTIONS. |
| 10) ROOF PLAN, ONE AREA SHOWS 1554 SF & |
| WALL AREA 6450 SF FOR A TOTAL OF 8004 SF |
| THIS AREA WILL REQUIRE TWO 4" ROOF |
| DRAINS. TWO 3" DRAINS ARE SHOWN. TABLE |
| 1106.2 - THE SCUPPER SHOWN IN THIS ARE |
| IS NOT SIZED FOR THIS AREA. SCUPPER SIZE |
| SHALL MINIMUM 85 SQ. IN. SECTION 1107.3 |
| - THE AREA WITH FOUR DRAIN WITH A SQUARE |
| FOOTAGE OF 2580 SF AND WALL AREA OF 326 |
| SF SHOWS NO SCUPPERS FOR THESE AREAS. - |
| SECTION 1503.4.2 STATES "SCUPPER SHALL |
| BE LOCATED AS CLOSE AS PRACTICAL TO REQ- |
| UIRED VERTICAL LEADERS. THIS DOES NOT |
| COMPLY WITH THE INTENT OF THE CODE. |
| 11) SHT A-5 "SCUPPER SEE SHT A-6 DETAIL |
| "A". NO DETAIL A ON SHT A-6, SCUPPER DE- |
| TAIL IS #1. PLEASE CORRELATE PLANS. SEC- |
| TION 104.2.1 |
| 12) SHT A-6 DETAIL #1 SCUPPER INDICATE A |
| 3"X15" SCUPPER, SECTION 1503.4.2 STATES |
| THAT SCUPPERS SHALL BE A MINIMUM OF 4" |
| IN HEIGHT. SUBMIT NEW SCUPPER DETAIL. |
| SHOW TYPE OF MATERIAL USED FOR SCUPPERS. |
| SECTION 104.2.1 |
| 13) IN ADDITION TO THOSE ACCESSIBLE |
| SLEEPING ROOMS AND SUITES REQUIRED BY |
| 11-9.1.2, SLEEPING ROOMS AND SUITES THAT |
| COMPLY WITH 11-9.3 (VISUAL ALARMS, NOTI- |
| FICATION DEVICES, AND TELEPHONES) SHALL |
| BE PROVIDED. 3 UNITS ARE REQUIRED PER |
| SECTION 11-9.1.3. PROVIDE INFORMATION |
| SHOWING WHICH ROOMS ARE IN COMPLIANCE. |
| 14) SHT A-14 DETAILS 1 & 3, SHOW DETAILS |
| PER SECTIONS 11-4.16.2 CLEAR FLOOR SPACE |
| 11-4.16.3 HEIGHT, 11-4.16.4 GRAB BARS, |
| 11-4.16.5 FLUSH CONTROLS. |
| 15) SHOW LOCATION FOR HDCP KING SUITE. |
| NONE SHOWN ON FLOOR PLAN, BUT SHT A-1.2 |
| INDICATES THERE IS ONE. SECTION 104.2.1 |
| 16) ALL PLUMBING & MECHANICAL SHEETS, |
| A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| SPECIFICATIONS, REPORTS AND FINAL BID |
| DOCUMENTS PROVIDED TO THE OWNER OR THE |
| OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| MENTS PREPARED OR ISSUED BY SAID REGIS- |
| TRANT AND BEING FILED FOR PUBLIC RECORD. |
| THE DATE THAT THE SIGNATURE AND SEAL IS |
| AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| UNDER THE SIGNATURE OF THE PROFESSIONAL |
| ENGINEER, FAC 61G15-23.002(1) |
| FS 471.025 |
| EACH SHEET OF PLANS AND PRINTS WHICH |
| MUST BE SEALED UNDER THE PROVISIONS OF |
| CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| DATED BY THE PROFESSIONAL ENGINEER IN |
| RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| FS 471.025 |
| - THE SIGNATURES ON THESE SHEETS ARE |
| COPIES, AND AS SUCH THEY ARE NOT APPROV- |
| ED. A "WET SIGNATURE" IS REQUIRED ON THE |
| SEAL OF EACH SHEET. |
| 16) SHT P-2.1 A VENT IS REQUIRED FOR THE |
| FLOOR DRAIN AND SPA DRAIN. SECTION 901.2 |
| .1 |
| 18) SHTS P-2.1 & P-2.2 SHOW NUMEROUS 2" |
| ROOF DRAIN LINES. WHAT ARE THESE LINES |
| DRAINING AND WHERE DO THEY TERMINATE. |
| PLEASE CLARIFY. SECTION 104.2.1 |
| 19) SHT P-2.1 NO SANITARY DRAIN LINE |
| SHOWN FOR WATER CLOSET IN TOILET ROOM |
| AT WORKSHOP/MAINT. SECTION 104.2.1 |
| 20) SHTS P-2.5 & P-2.6 RISERS A, C, K, |
| M, O, P, Q, & R FIXTURE SK-2 IS SHOWN AS |
| AN "S" TRAP. THIS IS NOT APPROVED PER |
| SECTION 1002.3. - THE SK-2 SINK SHALL |
| NOT CONNECT BELOW THE SLAB AS SHOWN, BUT |
| SHOULD CONNECT 18" TO 20" ABOVE THE SLAB |
| SECTION 104.2.1 |
| 21) SHTS P-2.5 & P-2.6 IDENTIFY ALL FIX- |
| TURES ON THE RISERS. SECTION 104.2.1 |
| 22) SHTS P-2.5 & P-2.6 MANY RISERS DO |
| NOT REFLECT THE FLOOR PLANS. PLEASE |
| CORRELATE THE RISERS AND FLOOR PLANS. |
| SECTION 104.2.1. |
| 23) SUBMIT WATER RISER ISOMETRICS FOR |
| EACH UNIT. SHOW ALL PIPE SIZING AND SHOW |
| WATER HAMMER ARRESTORS REQUIRED BY SECT- |
| ION 604.9 AND LOCATED NEAR THE FIXTURE, |
| NOT IN THE CEILING PER PDI-WH 201. |
| SECTION 104.3.1.1. |
| 24) SUBMIT A SANITARY BLDG DRAIN ISOMET- |
| RIC SHOWING ALL PIPE SIZES AND DFU'S AS |
| THEY ACCUMULATE IN THE SYSTEM. SECTION |
| 104.3.1.1. |
| 25) SUBMIT A STORM BLDG DRAIN ISOMETRIC |
| SHOWING ALL PIPE SIZES AND SQUARE FOOT- |
| AGE AS IT ACCUMULATES IN THE SYSTEM. |
| SECTION 104.3.1.1. |
| 26) SUBMIT STORM RISER DIAGRAMS SHOWING |
| PIPE SIZES AND SQUARE FOOTAGE. SECTION |
| 104.3.1.1 |
| 27) INFORMATIONAL: A SEPARATE GAS PERMIT |
| AND SEPARATE IRRIGATION PERMIT REQUIRED. |
| 28) SHT G-1.1 GAS CONNECTION SCHEDULE |
| INDICATES KITCHEN EQUIPMENT MAY BE IN- |
| STALLED. THIS IS NOT SHOWN ON THE RISER |
| DIAGRAM. PLEASE CLARIFY SECTION 104.2.1. |
| 29) SUBMIT MANUF. SPECIFICATION SHEETS |
| FOR THE REGULATORS. |
| 30) SHT G-1.1 A SHUT OFF VALVE AND A |
| UNION ARE REQUIRED UPSTREAM OF THE REGU- |
| LATORS. |
| 31) FOLLOWING INFORMATION REQUIRED FOR |
| GAS APPROVAL/PERMIT. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. NO PIPING SHOWN TO METER. |
| B. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). - PLANS SHOW |
| 255' TO METER, BUT CUT SECTIONS OF PIPE |
| ADD UP TO 190'. PLEASE SHOW ALL CUT SEC- |
| TIONS OF PIPE SO THAT PLANS CORRELATE. |
| C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| |
| REVIEW BY KEN STEVENS |