Plan Review Notes
Plan Review Notes For Permit 04051040
Permit Number 04051040
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT SP-1 RPZ BACKFLOW IS REQUIRED ON
 THE WATER SERVICE. PLAN SHOWS A BACKWAT-
 ER VALVE. SECTIONS 608.13.2 & 104.2.1.
 2) SHT SP-1 MORE INFORMATION REQUIRED ON
 THE ENTRANCE FOUNTAIN. WILL THERE BE A
 DRAIN AND OR WATER SUPPLY TO THE FOUNT-
 AIN? IF SO SHOW PIPING AND TERMINATION
 OF DRAIN AND THE WATER SUPPLY SHALL BE
 EQUIPPED WITH AN RPZ BACKFLOW. SECTION
 104.2.1.
 3) SHT A-1.1 THE FOLLOWING TOILET ROOMS
 SHALL BE ACCESSIBLE AND SHALL CONFORM TO
 SECTION 11-4.22. THE WORKSHOP/MAINT.,
 TOILET ROOMS AT LANUDRY ROOM, MENS AND
 WOMENS TOILET ROOMS NEAR THE EXERCISE
 ROOM. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.19, AND
 11-4.22 AND ALL SUBSECTIONS.
 4) SHT A-1.1 SINKS IN EMPLOYEE AREA ARE
 TO BE ACCESSIBLE. SUBMIT A DETAIL TO
 SHOW COMPLIANCE WITH 11-4.24 AND ALL
 SUBSECTIONS.
 5) ALL ARCHITECTURAL SHEETS SHALL SHOW
 THE PRINTED NAME OF THE PERSON RESPONSI-
 BLE FOR SEALING THE DOCUMENT. FAC
 61G1-16.004(6) & FS 481.2055.
 6) SHT A-4.1 ROLL IN SHOWER DETAIL SHOW
 DETAIL FOR SEAT 11-4.21.3, GRAB BARS 11-
 4.21.4, CONTROLS 11-4.21.5, SHOWER UNIT
 11-4.21.6.
 7) SHT A-4.2 SHOW A DETAIL FOR THE KING
 JAC SUITE THAT IS TO BE ACCESSIBLE.
 SECTION 104.2.1.
 8) SHT A-4.2 HDCP DETAILS, WATER CLOSET
 SHALL NOT BE IN THE TURNING AREA. THE
 AREA SHALL BE UNOBSTRUCTED PER SECTIONS
 11-4.2.3 & 11-4.22.3.
 9) SHT A-5 ROOF PLAN, SHOW GUTTER SIZE
 FOR LOWER FLAT ROOF. SHOW LOCATION OF
 DOWNSPOUTS. PLAN INDICATES THAT THE GUT-
 TER IS ON ALL SIDES OF ROOF. SHOW SQUARE
 FOOTAGE OF ROOF AND SHOW 1/2 AREA OF ALL
 VERTICAL WALLS ADDED TO AREA OF ROOF FOR
 SIZING GUTTERS AND DOWNSPOUTS PER SECT-
 IONS 1106 & 1107 AND ALL SUBSECTIONS.
 10) ROOF PLAN, ONE AREA SHOWS 1554 SF &
 WALL AREA 6450 SF FOR A TOTAL OF 8004 SF
 THIS AREA WILL REQUIRE TWO 4" ROOF
 DRAINS. TWO 3" DRAINS ARE SHOWN. TABLE
 1106.2 - THE SCUPPER SHOWN IN THIS ARE
 IS NOT SIZED FOR THIS AREA. SCUPPER SIZE
 SHALL MINIMUM 85 SQ. IN. SECTION 1107.3
 - THE AREA WITH FOUR DRAIN WITH A SQUARE
 FOOTAGE OF 2580 SF AND WALL AREA OF 326
 SF SHOWS NO SCUPPERS FOR THESE AREAS. -
 SECTION 1503.4.2 STATES "SCUPPER SHALL
 BE LOCATED AS CLOSE AS PRACTICAL TO REQ-
 UIRED VERTICAL LEADERS. THIS DOES NOT
 COMPLY WITH THE INTENT OF THE CODE.
 11) SHT A-5 "SCUPPER SEE SHT A-6 DETAIL
 "A". NO DETAIL A ON SHT A-6, SCUPPER DE-
 TAIL IS #1. PLEASE CORRELATE PLANS. SEC-
 TION 104.2.1
 12) SHT A-6 DETAIL #1 SCUPPER INDICATE A
 3"X15" SCUPPER, SECTION 1503.4.2 STATES
 THAT SCUPPERS SHALL BE A MINIMUM OF 4"
 IN HEIGHT. SUBMIT NEW SCUPPER DETAIL.
 SHOW TYPE OF MATERIAL USED FOR SCUPPERS.
 SECTION 104.2.1
 13) IN ADDITION TO THOSE ACCESSIBLE
 SLEEPING ROOMS AND SUITES REQUIRED BY
 11-9.1.2, SLEEPING ROOMS AND SUITES THAT
 COMPLY WITH 11-9.3 (VISUAL ALARMS, NOTI-
 FICATION DEVICES, AND TELEPHONES) SHALL
 BE PROVIDED. 3 UNITS ARE REQUIRED PER
 SECTION 11-9.1.3. PROVIDE INFORMATION
 SHOWING WHICH ROOMS ARE IN COMPLIANCE.
 14) SHT A-14 DETAILS 1 & 3, SHOW DETAILS
 PER SECTIONS 11-4.16.2 CLEAR FLOOR SPACE
 11-4.16.3 HEIGHT, 11-4.16.4 GRAB BARS,
 11-4.16.5 FLUSH CONTROLS.
 15) SHOW LOCATION FOR HDCP KING SUITE.
 NONE SHOWN ON FLOOR PLAN, BUT SHT A-1.2
 INDICATES THERE IS ONE. SECTION 104.2.1
 16) ALL PLUMBING & MECHANICAL SHEETS,
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 - THE SIGNATURES ON THESE SHEETS ARE
 COPIES, AND AS SUCH THEY ARE NOT APPROV-
 ED. A "WET SIGNATURE" IS REQUIRED ON THE
 SEAL OF EACH SHEET.
 16) SHT P-2.1 A VENT IS REQUIRED FOR THE
 FLOOR DRAIN AND SPA DRAIN. SECTION 901.2
 .1
 18) SHTS P-2.1 & P-2.2 SHOW NUMEROUS 2"
 ROOF DRAIN LINES. WHAT ARE THESE LINES
 DRAINING AND WHERE DO THEY TERMINATE.
 PLEASE CLARIFY. SECTION 104.2.1
 19) SHT P-2.1 NO SANITARY DRAIN LINE
 SHOWN FOR WATER CLOSET IN TOILET ROOM
 AT WORKSHOP/MAINT. SECTION 104.2.1
 20) SHTS P-2.5 & P-2.6 RISERS A, C, K,
 M, O, P, Q, & R FIXTURE SK-2 IS SHOWN AS
 AN "S" TRAP. THIS IS NOT APPROVED PER
 SECTION 1002.3. - THE SK-2 SINK SHALL
 NOT CONNECT BELOW THE SLAB AS SHOWN, BUT
 SHOULD CONNECT 18" TO 20" ABOVE THE SLAB
 SECTION 104.2.1
 21) SHTS P-2.5 & P-2.6 IDENTIFY ALL FIX-
 TURES ON THE RISERS. SECTION 104.2.1
 22) SHTS P-2.5 & P-2.6 MANY RISERS DO
 NOT REFLECT THE FLOOR PLANS. PLEASE
 CORRELATE THE RISERS AND FLOOR PLANS.
 SECTION 104.2.1.
 23) SUBMIT WATER RISER ISOMETRICS FOR
 EACH UNIT. SHOW ALL PIPE SIZING AND SHOW
 WATER HAMMER ARRESTORS REQUIRED BY SECT-
 ION 604.9 AND LOCATED NEAR THE FIXTURE,
 NOT IN THE CEILING PER PDI-WH 201.
 SECTION 104.3.1.1.
 24) SUBMIT A SANITARY BLDG DRAIN ISOMET-
 RIC SHOWING ALL PIPE SIZES AND DFU'S AS
 THEY ACCUMULATE IN THE SYSTEM. SECTION
 104.3.1.1.
 25) SUBMIT A STORM BLDG DRAIN ISOMETRIC
 SHOWING ALL PIPE SIZES AND SQUARE FOOT-
 AGE AS IT ACCUMULATES IN THE SYSTEM.
 SECTION 104.3.1.1.
 26) SUBMIT STORM RISER DIAGRAMS SHOWING
 PIPE SIZES AND SQUARE FOOTAGE. SECTION
 104.3.1.1
 27) INFORMATIONAL: A SEPARATE GAS PERMIT
 AND SEPARATE IRRIGATION PERMIT REQUIRED.
 28) SHT G-1.1 GAS CONNECTION SCHEDULE
 INDICATES KITCHEN EQUIPMENT MAY BE IN-
 STALLED. THIS IS NOT SHOWN ON THE RISER
 DIAGRAM. PLEASE CLARIFY SECTION 104.2.1.
 29) SUBMIT MANUF. SPECIFICATION SHEETS
 FOR THE REGULATORS.
 30) SHT G-1.1 A SHUT OFF VALVE AND A
 UNION ARE REQUIRED UPSTREAM OF THE REGU-
 LATORS.
 31) FOLLOWING INFORMATION REQUIRED FOR
 GAS APPROVAL/PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. NO PIPING SHOWN TO METER.
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - PLANS SHOW
 255' TO METER, BUT CUT SECTIONS OF PIPE
 ADD UP TO 190'. PLEASE SHOW ALL CUT SEC-
 TIONS OF PIPE SO THAT PLANS CORRELATE.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  