Plan Review Notes
Plan Review Notes For Permit 04051040
Permit Number 04051040
Review Stop M
Sequence Number 5
Notes
Date Text
2007-06-02 15:04:552ND REVIEW: DENIED
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. FIRE DAMPERS SHALL NOT BE LOCATED IN CLOTHES DRYER
 EXHAUST DUCTS. FBC,M 504.4.
  
 4. M-4: THE WALL BETWEEN "MECHANICAL" AND "VENDING" HAS
 BEEN CORRECTLY PROTECTED WITH A FIRE DAMPER. HOWEVER,
 THE FIRE DAMPER NOW SHOWN AT THE WALL BETWEEN "VENDING"
 AND THE CORRIDOR IS NOT NEEDED BECAUSE THIS WALL IS NOT
 RATED (NOTICE THERE IS NO DOOR ON THE WALL OPENING INTO
 THE VENDING AREA).
  
 5. OK
  
 6. M-5: SEE COMMENT #4
  
 7. OK
  
 8. M-9: NOT CORRECTED
  
 9. ONLY 2 SETS OF PLANS WERE SUBMITTED FOR A SECOND
 TIME. PLEASE PROVIDE 3 SETS AS PREVIOUSLY REQUESTED.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]