Plan Review Notes For Permit 04051040 |
Permit Number |
04051040 |
|
Review Stop |
M |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2007-06-02 15:04:55 | 2ND REVIEW: DENIED | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS REVIEW COMMENTS FOR CONTINUITY. | | | | 1. OK | | | | 2. OK | | | | 3. FIRE DAMPERS SHALL NOT BE LOCATED IN CLOTHES DRYER | | EXHAUST DUCTS. FBC,M 504.4. | | | | 4. M-4: THE WALL BETWEEN "MECHANICAL" AND "VENDING" HAS | | BEEN CORRECTLY PROTECTED WITH A FIRE DAMPER. HOWEVER, | | THE FIRE DAMPER NOW SHOWN AT THE WALL BETWEEN "VENDING" | | AND THE CORRIDOR IS NOT NEEDED BECAUSE THIS WALL IS NOT | | RATED (NOTICE THERE IS NO DOOR ON THE WALL OPENING INTO | | THE VENDING AREA). | | | | 5. OK | | | | 6. M-5: SEE COMMENT #4 | | | | 7. OK | | | | 8. M-9: NOT CORRECTED | | | | 9. ONLY 2 SETS OF PLANS WERE SUBMITTED FOR A SECOND | | TIME. PLEASE PROVIDE 3 SETS AS PREVIOUSLY REQUESTED. | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|