Plan Review Notes For Permit 04051040 |
Permit Number |
04051040 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-08-12 00:00:00 | DENIED: | | 1.PLAN SHEET M-2, M-4 & M-5, RELIEF | | GRILLE AT CORRIDOR WALL.IT APPEARS | | THIS WALL IS 1 HOUR FIRE RATED, THEREFOR | | FIRE DAMPERS ARE REQUIRED.DUCTS EXEMPT | | FROM HAVING FIRE DAMPERS SHALL COMPLY | | WITH 2001 FBC(M) 607.1.3 #3 ITEMS 1 | | THROUGH 4. | | 1. DUCTS SHALL NOT EXCEED 100 SQ IN. | | 2. SHALL BE A MINIMUM OF .0217 STEEL. | | 3. DUCT SHALL HAVE NO OPENINGS WITHIN | | 5 FT OF RATED WALL. | | 4. DUCT SHALL BE INSTALLED ABOVE THE | | CEILING. | | | | 2.ENERGY & MANUAL J CALCULATIONS WERE | | NOT PROVIDED. | | | | PROVISO: | | AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|