Plan Review Notes
Plan Review Notes For Permit 04051040
Permit Number 04051040
Review Stop M
Sequence Number 2
Notes
Date Text
2004-08-12 00:00:00DENIED:
 1.PLAN SHEET M-2, M-4 & M-5, RELIEF
 GRILLE AT CORRIDOR WALL.IT APPEARS
 THIS WALL IS 1 HOUR FIRE RATED, THEREFOR
 FIRE DAMPERS ARE REQUIRED.DUCTS EXEMPT
 FROM HAVING FIRE DAMPERS SHALL COMPLY
 WITH 2001 FBC(M) 607.1.3 #3 ITEMS 1
 THROUGH 4.
 1. DUCTS SHALL NOT EXCEED 100 SQ IN.
 2. SHALL BE A MINIMUM OF .0217 STEEL.
 3. DUCT SHALL HAVE NO OPENINGS WITHIN
 5 FT OF RATED WALL.
 4. DUCT SHALL BE INSTALLED ABOVE THE
 CEILING.
  
 2.ENERGY & MANUAL J CALCULATIONS WERE
 NOT PROVIDED.
  
 PROVISO:
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.