Plan Review Notes
Plan Review Notes For Permit 04051040
Permit Number 04051040
Review Stop M
Sequence Number 1
Notes
Date Text
2004-06-10 00:00:00DENIED:
 1.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE DRYERS.PLAN
 SHEET M2 APPEARS TO HAVE TWO COMMERCIAL
 DRYERS & DOMESTIC DRYERS ON THE 1ST &
 3RD FLOORS.
  
 2.COMMERCIAL DRYERS SHALL COMPLY WITH
 2001 FBC(M) 504.7.
  
 3.PLAN SHEET M1 MECHANICAL KEY NOTE
 #10, INSTALL BOOSTER FAN ABOVE THE
 CEILING.PROVIDE SUBMITTAL FOR THE
 BOOSTER FAN.SHOULD BOOSTER FAN FAIL,
 DRYER SHOULD NOT WORK.
  
 4.PLAN SHEET M2 INDICATES 10" X 8"
 DRYER EXHAUST RISER.PLEASE PROVIDE
 DETAIL OF RISER.PER 2001 FBC(M) 607.4
 DUCTS THAT PENETRATE MORE THAN ONE
 FLOOR SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE.WILL EACH DRYER RUN
 INDIVIDUALLY TO THE ROOF IN THE SAME
 RISE OR WILL A SUB-DUCT METHOD BE USED?
  
 5.CLEANOUTS REQUIRED ON THE VERTICAL
 RISERS PER 2001 FBC(M) 504.3.
  
 6.DRYER INSTALLATIONS THAT EXHAUST
 GREATER THAN 200 CFM, MAKE-UP AIR IS
 REQUIRED.
  
 7.PLAN SHEET M6 SINGLE EXHAUST RISER,
 PLEASE CLARIFY FIRE DAMPER AT THE TOP,
 IS THIS INTENDED AS A SUB-DUCT METHOD?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.