Plan Review Notes For Permit 04051040 |
Permit Number |
04051040 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-07-30 00:00:00 | 1) FIRE SPRINKLER HEADS SHALL BE | | QUICK RESPONSE OR LISTED | | RESIDENTIAL SPRINKLER HEADS. | | BUILDING IS USED FOR TRANSIENT LODGING. | | MUST COMPLY WITH APPLICABLE REQUIREMENTS | | | | 2) FIRE SPRINKLER PROTECTION REQUIRED | | ABOVE THE CEILING TO PROTECT THE | | WOOD TRUSSES. | | | | 3) SOFFITS SHALL NOT INTERFERE WITH | | THE OPERATION OF ANY FIRE SPRINKLER | | HEADS. | | | | 4) ALL VERTICAL SHAFTS THAT ARE LARGE | | ENOUGH FOR PERSONS TO FALL INTO MUST | | MARKED SHAFTWAY WITH 6" HIGH LETTERS. | | | | 5) ALL SMOKE DETECTORS SHALL BE | | INSTALLED A MINIMUM OF THREE FEET FROM | | AC DIFFUSERS. | | | | 6) NEW FIRE ALARM SYSTEM MUST BE | | UL LISTED FOR CENTRAL STATION SERVICE. | | | | 7) WHY IS THE OVERHAND NOT FIRE | | SPRINKLER PROTECTED. IS IT NOT FOUR | | FEET WIDE AND COMBUSTIBLE LUGGAGE | | DROPPED OFF THERE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|