Date Text
2004-07-30 00:00:001) FIRE SPRINKLER HEADS SHALL BE
 QUICK RESPONSE OR LISTED
 RESIDENTIAL SPRINKLER HEADS.
 BUILDING IS USED FOR TRANSIENT LODGING.
 MUST COMPLY WITH APPLICABLE REQUIREMENTS
  
 2) FIRE SPRINKLER PROTECTION REQUIRED
 ABOVE THE CEILING TO PROTECT THE
 WOOD TRUSSES.
  
 3) SOFFITS SHALL NOT INTERFERE WITH
 THE OPERATION OF ANY FIRE SPRINKLER
 HEADS.
  
 4) ALL VERTICAL SHAFTS THAT ARE LARGE
 ENOUGH FOR PERSONS TO FALL INTO MUST
 MARKED SHAFTWAY WITH 6" HIGH LETTERS.
  
 5) ALL SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF THREE FEET FROM
 AC DIFFUSERS.
  
 6) NEW FIRE ALARM SYSTEM MUST BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 7) WHY IS THE OVERHAND NOT FIRE
 SPRINKLER PROTECTED. IS IT NOT FOUR
 FEET WIDE AND COMBUSTIBLE LUGGAGE
 DROPPED OFF THERE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910