Plan Review Notes
Plan Review Notes For Permit 04051040
Permit Number 04051040
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-05-25 00:00:001) ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) SUITABLE ROADS ARE REQUIRED DURING
 CONSTRUCTION FOR FIRE AND PARAMEDICAL
 ACCESS.
  
 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 4) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWING. A MINIMUM OF AT LEAST
 6" HIGH NUMBERS ARE REQUIRED.
  
 5) A KNOX-BOX WILL BE REQUIRED.
  
 6) KNOX-BOX LOCKING CAPS WILL BE
 REQUIRED FOR THE FIRE DEPARTMENT
 CONNECTION.
  
 7) PLEASE PROVIDE PRODUCT APPROVALS
 FOR FIRE RATED GLAZING SHOWN ON
 PAGE A-1.1A.
  
 8) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 9) TACTILE SIGNAGE REQUIRED AT EXITS.
  
 10) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED SHAFTWAY WITH 6" HIGH LETTERS.
  
 11) OCCUPANT EMERGENCY INSTRUCTIONS
 SHALL BE POSTED. PLEASE INDICATE
 LOCATIONS.
  
 12) PLEASE INDICATE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL HANDRAILS
 AND GUARDRAILS.
  
 13) HOW DO THE SINGLE SMOKE DETECTOR
 IN ROOMS MEET THE CURRENT REQUIREMENTS.
  
 14) ELECTRONIC SWITCHES, CHAIN AND
 LOCK REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 15) NO FIRE SPRINKLER PLANS PROVIDED.
  
 16) PLEASE DISPLAY ALL FIRE EXTINGUISHER
 LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910