2004-05-25 00:00:00 | 1) ALL DEMOLITION, RENOVATION, AND |
| CONSTRUCTION TO COMPLY WITH NFPA 241. |
| |
| 2) SUITABLE ROADS ARE REQUIRED DURING |
| CONSTRUCTION FOR FIRE AND PARAMEDICAL |
| ACCESS. |
| |
| 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| TO, DURING AND AFTER CONSTRUCTION. |
| |
| 4) BUILDING ADDRESS NOT SHOWN ON |
| ELEVATION DRAWING. A MINIMUM OF AT LEAST |
| 6" HIGH NUMBERS ARE REQUIRED. |
| |
| 5) A KNOX-BOX WILL BE REQUIRED. |
| |
| 6) KNOX-BOX LOCKING CAPS WILL BE |
| REQUIRED FOR THE FIRE DEPARTMENT |
| CONNECTION. |
| |
| 7) PLEASE PROVIDE PRODUCT APPROVALS |
| FOR FIRE RATED GLAZING SHOWN ON |
| PAGE A-1.1A. |
| |
| 8) PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATIONS FOR WALLS AND CEILINGS. |
| |
| 9) TACTILE SIGNAGE REQUIRED AT EXITS. |
| |
| 10) ALL SHAFTS THAT ARE LARGE ENOUGH |
| FOR PERSONS TO FALL INTO MUST BE |
| MARKED SHAFTWAY WITH 6" HIGH LETTERS. |
| |
| 11) OCCUPANT EMERGENCY INSTRUCTIONS |
| SHALL BE POSTED. PLEASE INDICATE |
| LOCATIONS. |
| |
| 12) PLEASE INDICATE PRESCRIPTIVE |
| STRENGTH REQUIREMENTS FOR ALL HANDRAILS |
| AND GUARDRAILS. |
| |
| 13) HOW DO THE SINGLE SMOKE DETECTOR |
| IN ROOMS MEET THE CURRENT REQUIREMENTS. |
| |
| 14) ELECTRONIC SWITCHES, CHAIN AND |
| LOCK REQUIRED ON FIRE LINE BACKFLOW |
| DEVICE. |
| |
| 15) NO FIRE SPRINKLER PLANS PROVIDED. |
| |
| 16) PLEASE DISPLAY ALL FIRE EXTINGUISHER |
| LOCATIONS. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |