Plan Review Notes
Plan Review Notes For Permit 04051040
Permit Number 04051040
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-07 00:00:00************UNSAT ************
  
 1)NOTE: PLEASE PROVIDE WIND LOAD INFOR-
 -MATION PER FBC. 140 MPH FOR LT POLE/
 FIATURES.
  
 2)NOTE: POOL TO BE UNDER SEPARATE PERMIT
 ALL PHOTOMETRICS FOR SWIMMING POOLS
 AND SWIMMING AFTER DUSK MUST BE SUBMITT-
 -ED TO PALM BEACH COUNTY HEALTH DEPT.
 FOR REVIEW.
  
 3)NOTE: NOTED: LIGHTNING PROTECTION
 SYSTEM IF INSTALLED BY SUB CONTRACTOR
 AND NOT ELECTRICAL CONTRACTOR MUSTBE
 UNDER SEPARATE PERMIT.
  
 4)NOTE: NOTED: SATELITE DISH REQUIRES
 PERMIT MORE THAN 39". THIS IS ONLY A
 NOTE>
  
 5)NOTE: PLEASE SEE RECEPT SPACING FOR
 GUEST RMS TO MEET 210.52, PER 210.60
 PLEASE SEE A FEW LAYOUTS ON E-10,11
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]