Plan Review Notes
Plan Review Notes For Permit 04051040
Permit Number 04051040
Review Stop B
Sequence Number 9
Notes
Date Text
2005-07-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04051040
 ADD: 2485 METROCENTREBLVD
 CONT: PARAG CONSTRUCTION
 TEL: (754)264-6192
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW- REVISION
 ACTION: DENIED
  
 SHEET S-1 DETAIL # 1 INDICATES A 3"
 WASTE PIPE EMBEDDED IN THE MONOLITHIC
 SLAB, SEE
 P305.5 PIPES THROUGH OR UNDER FOOTINGS
 OR FOUNDATION WALLS. ANY PIPE
 THAT PASSES UNDER A FOOTING OR THROUGH A
 FOUNDATION WALL SHALL BE PROVIDED
 WITH A RELIEVING ARCH, OR A PIPE SLEEVE
 PIPE SHALL BE BUILT INTO THE
 FOUNDATION WALL.SUCH SLEEVE SHALL BE
 TWO PIPE SIZES GREATER THAN THE PIPE
 PASSING THROUGH THE WALL.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  