Plan Review Notes
Plan Review Notes For Permit 04051040
Permit Number 04051040
Review Stop B
Sequence Number 3
Notes
Date Text
2004-11-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04051040
 ADD: 2485 METROCENTRE BLVD
 CONT: PARAG CONSTRUCTION
 TEL: (754)264-6192
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 3RDREVIEW
 ACTION: DENIED
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 THE NOC BY FL STATE LAW NEEDS TO BE
 RE-RECORDED, NO WORK HAS STARTED AFTER
 90 DAYS OF RECORDING.
  
 2) SOILS REPORTS:
 A) (3) ORIGINAL SIGNED & SEALD SOILS
 REPORTS ARE REQUIRED.
 B) (3) ORIGINAL DENSITY REPORTS BY
 NUTTING.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3) PROVIDE ENERGY CALS, (3) REQUEST,
 FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 COMMENT# 7 FROM PREVIOUS REVIEW,
 THE DO NOT MATCH, THE FLOOR PLAN VS THE
 ELEVATION, ON THE ELEVATION (NORTH) OF
 SHEET A-1 (2) WINDOWS ARE MISSING ON
 EACH FLOOR. SEE ROOMS 100,102,104,106 &
 108. MISSING WINDOWS IN ROOMS 100 &
 108.
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR STEEL DOORS
 B) EXTEIOR GLAZED DOORS
 C) EXTERIOR AUTO FRONT ENTRY DOORS
 D) EFIS SYSTEMS
 E) WALL LOUVER
 F) STRUCTURAL COMPONENTS
 1) WOOD CONNECTORS/ TRUSS CONNECTORS
 2) EXTERIOR RAILINGS
 G) ROOF ASEMBLIES, FLAT, UNDERLAYMENT,
 ROOF TILES
  
 6)THE STRUCTURAL AND ARCHITECTURAL
 PLANS
 DO NOT PROVIDE SUFFICENT INFORMATION ON
 THE PORT COCHERE CEILING.NOTE (11) FROM
 THE PREVIOUS REVIEW.
 A) PROVIDE THE ATTACHMENT INFORMATION
 BE
 TWEEN THE METAL HIGH-HAT AND BAR JOIST.
 B) PROVIDE MANUFACTURERS RECOMMENDATION
 (APPROVAL) FOR EXTERIOR CEILINGS OR
 SOFFITS.
 C) SHEET A-5 PORT COCHERE DETAIL
 DOESN'T
 INDICATE THE FINISH MATERIAL TO BE USED
  
 OVER THE GYPSUM SHEATHING, PLEASE GIVE
 FINISH. NOTE UNDER LIMITATIONS FOR
 EXTER
 IOR GYPSUM SHEATHING IS NOT A SUITABLE
 SUBTRATE FOR THE DIRECT APLICATION OF
 STUCCO, PAINT OR TEXTURES.
  
 7) NOTE# 16 FROM THE PREVIOUS REVIEW,
 STORAGE ROOM NEXT TO THE STAIRWELL AT
 EACH END OF THE BUILDING DO NOT PROVIDE
  
 FIRE RATED DOORS, SEEA-6 DOOR SCHEDULE
 DOOR# 15. TABLE 704.1 OCCUPANCY SEPERA-
 TION S2 LOW HAZARD 2HR.
  
 7B) NOTE# 16 FROM THE PREVIOUS REVIEW:
 PROVIDE THE EQUIVALANT THICKNESS FOR THE
 BLOCK WALL SEPERATING THE STORAGE ROOMS
 AND SUITES. EQUIVALANT THICKNESS IS TO
 BE PROVIDED BY THE BLOCK MANUFACTURER
 FOR A 2 HR WALL, SEE 709.3.1.
  
 8) NOTE# 20 FROM PREVIOUS REVIEW:
 A) SHEET S-5 DETAIL "A" CORRECT SIZE OF
  
 BOLTS TO BE USED IN FOOTER 4-34/DIA.
 B) COLUMN SPLICE WHAT TYPE OF METALS
 ARE
 TO BE USED FOR THE "SPLICE" WHAT TYPE OF
  
 WELD & THICKNESS.
 C) STEEL COLUMN INDICATES THE USE OF A
 4"X4", BUT NO THICKNESS IS PROVIDED?
 D) SAME DETAIL CAP PLATES INDICATE SEE
 COLUMN SCHEDULEFOR THE SIZE BUT WHERE?
 PROVIDE THE SIZE, THICKNESS AND THE
 WELD
 AND THE AMOUNT OF WEIGHT TO BE
 RESISTED.
 ARE GUSSET PLATES REQUIRED FOR UNDER THE
  
 CAP PLATES?
  
 9) MISSING THE ROOF FRAMING IN REGAURDS
  
 TO THE CONCRETE ROOF DECK.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026