Plan Review Notes
Plan Review Notes For Permit 04051040
Permit Number 04051040
Review Stop B
Sequence Number 2
Notes
Date Text
2004-08-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04051040
 ADD: 2485 METROCENTRE BLVD
 CONT: PARAG CONSTRUCTION
 TEL: (561)767-0398
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 "*" THIS SYMBOL MEANS THE CODE ARTICLE
 REFRENCED IS A W.P.B. AMENDMENT.
  
 2ND REVIEW
 ACTION: DENIED
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1) NOTICE OF COMMENCEMENT- WILL HAVE TO
 BE REFILED, NO WORK COMMENCED WITHIN 90
 DAYS OF BEING RECORDED WILL REQUIRE NOC
 TO BE REFILED.
  
 2) SOILS REPORTS SUBMITTED HAVE TO BE
 SIGNED AND SEALED (3).
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION. 2ND REQUEST!
  
 4) FBC* 105.3 RESIDENT INSPECTOR.
 THE SUBMITTED RESUME IS OK BUT A MEETING
 WITH HAROLD PISKURA AND DOCUMENTS TO BE
 SIGNED ARE REQUIRED BEFORE A PERMIT CAN
 BE ISSUED.
  
 5) PROVIDE (3) SETS OF ALL PLANS, SPECS,
 TEST, AND PRODUCT APPROVALS, PART OF THE
 RESIDENT INSPECTOR PROGRAM. 2ND REQUEST!
  
 6) PLANS DO NOT PROVIDE WHAT ELEVATION
 THE FIRST FLOOR WILL BE SET AT? BUILDING
 WILL BE IN A FLOOD ZONE, PROVIDE AN ELE.
 ON PLANS, FIRST FLOOR MINIMUM ELEVATION
 IS 16'-6". FLOOD ZONE A-8 MINIMUM FINISH
 FLOOR ELE IS 16'-6", A FLOOD ZONE ELEVA-
 TION CERTIFICATE WILL BE REQUIRED BEFORE
 A C.O. WILL BE ISSUED. 2ND REQUEST.
  
 7)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, PLANS
 DO NOT MATCH, 2ND REQUEST, RE-EVALUATE
 END ZONE PRESSURES FOR ROOMS 100, 200 &
 300. SHEET A-1.1 INDICATES (5) WINDOWS
 ALONG ROOMS 100, 102, 104, 106, AND 108.
 THE ELEVATIONS ON SHEET A-1 NORTH ELEVA-
 TION ONLY INDICATES (3) WINDOWS PER
 FLOOR!!!!! PROVIDE WINDOWS ON ELEVATIONS
 AND THE PRESSURES FOR THE END ZONES!!!!
 2ND REQUEST!
  
 8)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 2ND REQUEST!
  
 9) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS REPORTS SUBMITTED CHARTS ARE
 ILLEGIBLE. CIRCLE THE TYPE GLASS TO BE
 USED (A-E2).
 B) SPANDREL GLASS HAS A ARCHED HEAD,FIX-
 ED GLASS PROVIDE REPORT.
 C) MULLIONS- THE SPANDREL GLASS SYSTEM
 SPANS 3 STORIES (WEST ELE), PROVIDE
 DETAILS AS TO WHERE THE HORIZONTAL AND
 VERTICAL MULLIONS ARE TO BE JOINED.
 CHARTS ARE GOOD TO 53"X 74"?
 D) PROVIDE MULLION REPORT FOR RADIUS
 HEAD USED IN SPANDREAL SYSTEM.
 E)EXTERIOR STEEL DOORS, AUTO FRONT ENTRY
 DOORS, OR GLAZED ENRTY DOORS.
 F) EFIS SYSTEMS,
 G) WALL LOUVERS
 H) STRUCTURAL COMPONENTS-
 1- WOOD CONNECTORS/ TRUSS CONNECTORS
 2- EXTERIOR RAILINGS
 I) ROOFING ASSEMBLIES, FLAT, UNDERLAY-
 MENTS, ROOF TILE.
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 11)STRUCTURAL NOR ARCHITECTURAL PLANS DO
 NOT PROVIDE DETAILS AS HOW THE CEILING
 OF THE PORT COCHERE WILL BE MADE OF OR
 HOW OFTEN?SECTION A/S-4.
  
 12) FLORIDA ACCESSIBILITY CODE, PORT
 COCHERE 11-4.6.6. PASSENGER LOADING
 ZONE, THE PLANS DO NOT PROVIDE INFORMA-
 TION FOR THE PASSENGER LOADING ZONE
 UNDER THE PORT COCHERE.IS THERE A RAISED
 WALKWAY, CURBCUT AND HOW IS THE PASSEN-
 GER LOADING ZONE MARKED? 2ND REQUEST!
  
 13) SHEET A-1.1C LAUNDRY ROOM RESTROOM,
 THE DOORWAY TO THE RESTROOM IS NOT
 ACCESSIBLE. SEE CLEAR WIDTH 11-4.3.3 IF
 A PERSON INA WHEELCHAIR MUST MAKE A
 TURN AROUND AN OBSTICLE, THE MINIMUM
 CLEAR WIDTH OF AN ACCESSIBLE ROUTE SHALL
 BE AS SHOWN IN FIGURE 7(A) AND 7(B).SEE
 7(B) WHEN X< 48". ONCE AROUND THE WALL
 THE SWING OF THE DOOR MAKES IT IMPOSS-
 IBLE TO HAVE A CLEAR FLOOR SPACE 30'X48"
  
 14) LAUNDRY ROOM: LAUNDRY CHUTE,
 A) THE TERMINATION ROOM REQUIRES A 3/4
 HOUR RATED DOOR SEE TABLE 705.1.2.
 B) TRASH CHUTE ACCESS ROOMS ON THE 2ND
 AND 3RD FLOOR ALSO REQUIRE A 3/4HR DOOR.
 SEE DOOR # 5 IN SCHEDULE.
 C) SHEET A-13 LAUNDRY CHUTE SECTION,
 SEE UL U401 THIS DECRIPTION VERSES WHAT
 IS SPECED ON THE PLANS IS A DESREPANCY,
 PLASTER, METAL LATH AND WIRE STUDS.
 D) 705.2.4.6 AN AUTOMATIC FIRE SPRINK-
 LER SYSTEM SHALL BE INSTALLED AT THE TOP
 AND ALTERNATE FLOOR LEVELS IN REFUSE AND
 LAUNDRY CHUTES AND TERMINATION ROOMS.
  
 15) SHEET A-12 ROOF STAIR PLAN REVISED
 TO REFLECT A WALL BETWEEN THE STAIRWELL
 AND STORAGE ROOM. THE DOOR SCHEDULE LIST
 THIS DOOR AS #15, NO MENTION OF 3/4 HR
 RATING, TABLE 705.1.2.
  
 16) SHEET A-12 DETAILS OF STAIR PLANS
 INDICATE STORAGE UNITS NEXT TO ALL THE
 STAIRWELLS, REQUIRING 2HR WALLS(TABLE
 704.1 STORAGE LOW HAZARD) THIS ALSO WILL
 REQUIRE RATING AT DOORS. ALSO PROVIDE
 THE EQUIVALENT THICKNESS OF THE 6" BLOCK
 TO BE PROVIDED BY THE BLOCK MANUFACTURER
 FOR A 2 HR WALL. ROOF STAIR PLAN INDICI-
 CATES DOOR# 15 WITH NO RATING 3/4 HR
 RATING REQUIRED, 705.1.2.
  
 17) SHEET S-4 WIND DESIGN CRITERIA STILL
 NEEDS CORRECTING, THE EXPOSURE CATEGORY
 IS A "B" DO NOT USE THE CODE SECTION
 1619.2 HIGH WIND BROWARD COUNTY, BROWARD
 COUNTY REQUIRES A "C" EXPOSURE.IF DESIGN
 ING TO THIS THE PRESSURE ZONES AND MULTI
 PLIERS ARE TO BE APPLIED.
  
 18) SHEET A-6, S-4 BOTH INDICATE THE USE
 OF WOOD TRUSSES FOR THE ROOF, UNDER THIS
 REVIEW THIS BUILDING IS A TYPE IV UNPRO-
 TECTED/ SPRINKLERED, TABLE 600 REQUIRES
 THE ROOF TO BE NONCOMBUSTIBLE, 2 STORIES
 MAY USE FIRE RETARDANT TREATED PLYWOOD.
 DEPENDING ON THE CLASSIFICATION OF THIS
 BUILDING ADDITIONAL COMMENTS MAY RISE TO
 THE ATTACHMENT OF ROOF TILE TO THE SUB-
 STRATE.
  
 19) SHEET S-4 CANTILEVERED CANOPY.SHEET
 S-4 DETAIL"C"MISSING WELD THICKNESS,
 THICKNESS OF STEEL PIPE, DESCEPANCY
 BETWEEN S-4 & A-5, S-4 SHOWS AN ENBED IN
 A 8" WALL WHEREAS A-5 SHOWS THE ENDBED
 IN THE END OF A POURED 6" WALL.THE PLATE
 SIZES ARE ALSO 2" IN DIFFERENCE.PROVIDE
 ADDITIONAL DETAILS FOR COVERAGE OVER THE
 STUDS IN THE EMBEDS.2ND REQUEST.
  
 20 A)SHEET S-5 DETAILS"A" CORRECT SIZE
 BOLTS TO BE USED IN FOOTER 4-34/DIA. AB
 B) COLUMN SPLICE WHAT TYPE OF METALS ARE
 TO BE USED FOR "SPLICE" WHAT TYPE OF
 WELD AND THICKNESS.
 C) STEEL COLUMNS INDICATE SIZE 4"X4" BUT
 NO THICKNESS PROVIDED?
 D) SAME DETAIL CAP PLATES INDICATE SEE
 COLUMN SCHEDULE FOR SIZE BUT WHERE?
 PROVIDE SIZE, THICKNESS AND WELD AND THE
 AMOUNT OF WWEIGHT TO BE RESISTED. WELD
 AND THICKNESS,ARE GUSSET PLATES REQUIRED
  
 21) SHEET S-5 DETAIL"C", PROVIDE THE
 DESIGN LOAD FOR THE 6" BLOCK, ACI 530-99
  
 22) MISSING THE ROOF FRAMING IN REGAURDS
 TO THE CONCRETE ROOF DECK.
  
 23) PROVIDE FIRE SPRINKLER PLANS BEFORE
 PERMIT CAN BE ISSUED. 2ND REQUEST.
  
 24)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL (561)805-6715
 FAX (561)659-8026