2004-06-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04051040
 ADD: 2485 METROCENTRE BLVD
 CONT: PARAG CONSTRUCTION
 TEL: (561)767-0398
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 4) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
 ***PROVIDE (3) SETS OF ALL PLANS, SPECS,
 TEST AND PRODUCT APPROVALS.*************
  
 5)903.8.2 FLOR ST STATUTE 553.895(2)
 ALL RESIDENTIAL BUILD. 3 OR MORE STORIES
 TALL WHETHER DESIGNATED AS TOWNHOUSE,
 CONDOMINIUMS, "APARTMENT HOUSES,
 TENEMENTS, GARDEN APARTMENTS OR BY ANY
 OTHER NAME SHALL BE SUPPLIED BY FIRE
 SPRINKLERS MEETING NFPA 101.
  
 6) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". FLOOD ZONE A-8
 MINIMUM FINISH FLOOR ELEVATION 16'-6".
  
 7) PLANS DO NOT PROVIDE THE MINIMUM
 BUILDING TYPE DESIGN CRITERIA?
  
 8)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 6) RE-EVALUATE END ZONES, EAST END,
 ROOMS 100,200 & 300, LOW PRESSURE.
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED OR OPERATABLE
 B) MULLIONS
 C) EXTERIOR DOORS
 D) STOREFRONT SYSTEMS
 E) EFIS SYSTEMS
 F) WALL LOUVERS
 G) ROOFING
 H) SHUTTERS
 I) STRUCTURAL COMPONENTS, WOOD CONNECT
 ORS, TRUSS ANCHORS AND RAILINGS
  
 8)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 11)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 12)FLORIDA ACCESSIBILITY, PORTICO
 11-4.6.6 PASSENGER LOADING ZONE, PLANS
 DO NOT PROVIDE INFORMATION FOR THE PASS-
 ENGER LOADING ZONE UNDER THE PORTICO.
  
 13) SHEET SP-1 PLANS INDICATE A TRANSFOR
 MER NEXT TO A SIDEWALK, BEFORE THE TRANS
 FORMER THE SIDEWALK IS A MINIMUM OF 44"
 WHICH IS CORRECT FOR A MEANS OF EGRESS.
 THIS SIDEWALK IS PART OF THE EXIT DIS-
 CHARGE REQUIRING A CONTINIOUS 44".
 SEE DEFINTIONS, MEANS OF EGRESS.
  
 14)DOOR BETWEEN THE EXERCISE ROOM TO THE
 SPA DRAWN IN AT 2'-0" NOT 3'-0", ALSO
 THISDOOR REQUIRES 18"ON THE PULL SIDE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 15) EXIT STAIR TOWERS INDICATE THE USE
 OF A 1 HR "C" LABEL DOOR, SEE 705.1.3.4
 REQUIRING A 1 HR "B" OR AVERAGE TEMPERA-
 TURE RISE DEVELOPED ON THE UNEXPOSED
 SIDE SHALL NOT EXCEED 450 DEGRESS AT THE
 END OF 30 MINUTES OF STANDARD FIRE TEST
 EXPOSURE.
  
 16) SHEET A-1.1B INDICATES AN 1/8" SCALE
 BUT IS ACTUAL 1/4".
  
 17) SHEET A-1.1B WORKSHOP MAINTANCE ROOM
 TOILET ROOM AND BY THE EXERCISE ROOM ARE
 REQUIRED TO BE ACCESSIBLE. SEE COMMON
 USE AND ACCESSIBLE. 11-4.1.3(11)THE
 SAME HOLDS TRUE WITH LAUNDRY RESTROOM.
  
 18)THE MAINTANCE ROOM RESTROOM DOOR WILL
 NEED TO BE A 36" DOOR.
  
 19) LAUNDRY ROOM: LAUNDRY CHUTE,
 A) TERMINATION ROOM, REQUIRES A 3/4 HR
 DOOR, SEE TABLE 705.1.2.
 B) ACCESS ROOMS DOORS ON THE 2ND & 3RD
 FLOORS ALSO REQUIRE A 3/4 HR DOOR.
 SEE 705.2.4.3.
 C) SHEET A-13 DETAIL "C" INDICATES A
 UL-U411 (2HR) WALL. YOUR DETAIL ALSO HAS
 DRYWALL ON 1 SIDE OF THE STUDS? PROVIDE
 THE CORRECT UL LISTING FOR A 1 HR SHAFT
 ENCLOSURE (LAUNDRY CHUTE) LESS THAN
 4 STORIES.
 D) 705.2.3.4.2. WHEN A SHAFT EXTENDS
 THROUGH THE ROOF, THE SHAFT ENCLOSURE
 SHALL SHALL EXTEND AT LEAST 36" ABOVE
 THE HIGHEST PART OF THE ROOF THAT IS
 WITHIN 5 FT OF THE OPENING. THE ENCLO-
 SURE WALL OR COMBINATION OF ENCLOSURE
 WALL OR COMBINATION OF ENCLOSURE WALL
 AND GUARDRAIL SHALL BE AT LEAST 42" HIGH
 E) 705.2.4.6. AN AUTOMATIC FIRE SPRINK-
 LER SYSTEM SHALL BE INSTALLED AT THE TOP
 AND ALTERNATE FLOOR LEVELSIN REFUSE AND
 LAUNDRY CHUTES AND TERMINATION AND
 INCINERATION ROOMS.
  
 20)SHEET A-12 ROOF STAIR PLAN, INDICATES
 STORAGE COMPARMENT IN THE STAIRWELL.
 1006.1.3 A STAIRWELL ENCLOSURE SHALL NOT
 BE USED FOR ANY PURPOSE OTHER THAN A
 MEANS OF EGRESS.
  
 21) SHEET A-11A SEE DESIGN CRITERIA FOR
 EXTERIOR WALL FRAMING, CORRECT CODE REF-
 RENCED AND WIND SPEED.
  
 22) SHEET S-4 WIND DESIGN DOESN'T INDI-
 CATE IF DESIGNED TO 1606.6 OR ASCE 7-98.
 A) DESIGN CRITERIA IS FOR A ONE STORY
 STRUCTURE MRH 17'-6".
 B) LOW PRESSURES!!!!
 C) DESIGN CHART IS FOR < 30'.SEE
 SHEET A-1 WEST ELE. MEAN ROOF > 30'.
  
 23) SHEET S-4 PORTE COCHERE SECTION
 INDICATES CEMENT ROOF TILE ATTACHED DIR-
 ECTLY TO STEEL DECK, PROVIDE PRODUCT
 TESTING REPORT WITH THIS APPLICATION.
 THERE IS NOT ENOUGH INFORMATION SUBMITT-
 ED FOR STRUCTURAL REVIEW OF THE PORTE
 COCHERE.
  
 24) SHEET S-4 CANTILEVERED CANOPY.
 PLANS DO NOT GIVE INFORMATION REQUIRED
 FOR STRUCTURAL REVIEW.S-4 & A-5 INDICATE
 TENSION CABLES BEING USED AND ANCHORED
 INTO A EXTERIOR STEEL STUD WALL, NO
 DETAILS.
  
 25) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS ARE INSUFICIENT FOR THE ELEVATION
 CONTAINING THE SPANDRIAL GLASS.
 A) SHEET A-10 INDICATES THE GABLE END
 BRACING DUT A-6 DETAIL DOESN'T GIVE THE
 CORRECT DETAIL, THERE SHOULD BE A
 CONCRETE DECK, PT LEDGER THEN THE GABLE
 END, NO CONNECTION DETAILS GIVEN.
 B) BENEATH THE CONCRETE DECK THERE IS A
 METAL FRAMED WALL, WHERE IS THE GLASS
 TO END?
 C) SHEET A-6 GABLE END DOES NOT PROVIDE
 WHAT TYPE FRAMING IS TO BE USED FOR THE
 VERTICAL BRACE, HOW OFTEN THE BRACE IS
 TO BE INSTALLED OR LENGHT OF BRACE.
 D) SHEET A-6 GIVES DETAIL ON VENTING
 BUT NO INFORMATION ON HOW OFTEN THE
 ROOF VENTS ARE REQUIRED.
  
 26) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 27)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 28)IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026