| 2005-04-13 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1) SHTS P-2.1 & P2.6 WATER CLOSET NOT |
| | VENTED. RISER SHALL CONNECT DOWNSTREAM |
| | OF THE VENTED LINE. SEE RISER "V" |
| | 2) SHT P-2.1 & P2.6 MORE INFORMATION IS |
| | REQUIRED FOR THE SPA. MANUF INFORMATION |
| | IS REQUIRED TO SEE HOW THE DRAIN FOR THE |
| | SPA WILL BE PIPED TO THE HUB DRAIN. |
| | SECTION 104.2.1. |
| | 3) SHT P-2.1 GREASE TRAP IN THE PANTRY |
| | IS NOT APPROVED. PLEASE CONTACT RODNEY |
| | COMPO, ENVIRONMENTAL COMPLIANCE FOR THE |
| | GREASE TRAP REQUIREMENTS. (561) 805 2272 |
| | OR E-MAIL [email protected]. WASTE ORD. |
| | #2938-96. |
| | 4) IF FOOD IS BEING PREPARED ON SITE FOR |
| | PUBLIC CONSUMPTION THE HEALTH DEPT WILL |
| | BE REQUIRED TO BE NOTIFIED. NOTIFY THE |
| | PALM BEACH COUNTY HEALTH UNIT, DIVISION |
| | OF ENVIRONMENTAL HEALTH. (561) 355-3018. |
| | PLEASE CLARIFY. - ALSO IF FOOD IS BEING |
| | PREPARED, THE SINKS IN THE FOOD PREP |
| | AREA SHALL BE INDIRECT WASTED PER |
| | SECTION 802.1.1. |
| | 5) SHT P-2.1 SK3 SINK IS NOT SHOWN ON |
| | THE FLOOR PLAN. THE SANITARY PIPING IS |
| | SHOWN FOR THIS SINK IN THE PANTRY AREA. |
| | 6) SHT P-2.1 RAIN WATER LEADER (9) IS |
| | POINTING TO THE SANT. RISER AT |
| | REGISTRATION AREA. SECTION 104.2.1. |
| | 7) SHT P-2.1 ISOMETRIC SANT. RISER |
| | DIAGRAMS ARE REQUIRED FOR THE PIPING TO |
| | THE EXERCISE ROOM/SPA, FLOOR DRAIN, |
| | DRINKING FOUNTAIN, PANTRY AREA, AND THE |
| | EMPLOYEE AREA. SECTION 104.3.1.1. |
| | 8) SHTS P-2.1, & P-2.2 AND ASSOCIATED |
| | RISER DIAGRAMS, ALL SAFEWASTES ARE NOT |
| | APPROVED. SEE SPA DRAIN, FLOOR DRAIN |
| | FROM TRENCH DRAIN, & FLOOR DRAIN IN THE |
| | EMPLOYEE AREA UPSTREAM OF THE MOP SINK. |
| | ALL FLOOR DRAINS SHALL HAVE A SEPARATE |
| | TRAP AND CONNECT AT THE VENTED LINE |
| | SEPARATELY. |
| | 9) SHT P-2.1 6" REQUIRED ON THE BUILDING |
| | DRAIN DOWNSTREAM OF THE "W" RISER |
| | DIAGRAM. SHOWS 175 DFU BUT RECHECKING |
| | THE FIGURES, THEY ADD UP TO 183 DFU. |
| | 10) SHTS P-2.1, P-2.2, P-2.5, & P-2.6 |
| | CHECK ALL ADDITION OF FIXTURE UNITS ON |
| | THE RISERS AND THE ACCUMULATED FIXTURE |
| | UNITS IN THE BUILDING SANT. DRAIN. THERE |
| | IS A DISCREPANCY IN THE NUMBERS. SECTION |
| | 104.2.1. |
| | 11) SHTS P-2.2 & P-2.5 W/C NOT VENTED |
| | AND HORIZONTAL DRY VENT NOT APPROVED. |
| | SEE RISER D&E. SECTIONS 901.2.1, 905.3, |
| | AND 905.4 |
| | 12) SHTS P-2.1 & P-2.2 VENT NOT SHOWN ON |
| | THE LINE DOWNSTREAM OF THE 4" TRENCH |
| | DRAIN. SECTION 104.2.1. |
| | 13) SHT P-2.5 SANT. RISER "X" DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| | CODE REQUIREMENTS. NO HUB DRAINS ARE |
| | SHOWN ON THE FLOOR PLAN FOR THE SECOND |
| | AND THIRD FLOORS. SANT. DRAIN LINE SHALL |
| | NOT BE REDUCED IN THE DIRECTION OF FLOW. |
| | SECTION 704.2. SEE TUB/SHR RISER |
| | SECTION. |
| | 14) SHT P-2.5 SANT. RISER "Q" DOES NOT |
| | REFLECT THE FLOOR PLAN. NO WASH MACHINE |
| | IS SHOWN ON THE 2ND FLOOR OF THE FLOOR |
| | PLAN. SECTION 104.2.1. |
| | 15) SHT P-2.6 SANT. RISER "M" DOES NOT |
| | REFLECT THE FLOOR PLAN. THE TUB/SHR AND |
| | SK-2 LAYOUT ON THE RISER DOES NOT |
| | REFLECT THE FLOOR PLAN LAYOUT. SECTION |
| | 104.2.1. |
| | 16) SHT P-2.7 RECHECK ALL DRAINAGE |
| | FIXTURE UNITS AND PIPE SIZE. ALSO GREASE |
| | INTERCEPTOR NOT APPROVED. |
| | 17) SHT P-5.1 TYPICAL RAIN WATER |
| | ISOMETRIC DOES NOT REFLECT ALL RISER |
| | DIAGRAMS. PLEASE SUBMIT RISERS FOR EACH |
| | TYPE OF RWL. SECTION 104.3.1.1. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. - |
| | PLEASE RETURN THE RED LINE COPY OF THE |
| | REVISION TO HELP EXPEDITE REVISION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |