| 2007-05-10 13:39:19 | ---------------DENIED----------------- |
| | |
| | FBC 2001 CODE FAMILY |
| | FBC 2001 CH. 1 AS AMENDED BY THE CITY OF WEST PALM |
| | BEACH |
| | NFPA 90A-99 |
| | |
| | 1. M-2: PLAN SHOWS FIRE DAMPER IN WALL BETWEEN FRONT |
| | DESK OFFICE AND REGISTRATION. THIS WALL IS NOT SHOWN TO |
| | BE RATED ON ARCHITECTURAL PLAN (A-1.1B). PLEASE |
| | COORDINATE PLANS. FIRE DAMPERS SHALL BE INSTALLED PER |
| | MANUFACTURER'S INSTRUCTIONS AND IN LOCATIONS LISTED IN |
| | FBC,M 607.1.2. |
| | |
| | 2. M-2: CLOSET FOR AHU-5 IS DESIGNATED AS 'STORAGE' ON |
| | ARCHITECTURAL PLANS (A-1.1B). THIS ROOM IS A PLENUM AND |
| | SHOULD BE DESIGNATED AS A MECHANICAL CLOSET OR |
| | MECHANICAL EQUIPMENT ROOM PER FBC,M 602.1. PLENUMS |
| | SHALL NOT BE USED FOR OCCUPANCY OR STORAGE PER NFPA 90A |
| | SEC 2-3.10.2. |
| | |
| | 3. M-2: TWO 10" ROUND DRYER EXHAUST DUCTS ARE |
| | PENETRATING A WALL DESIGNATED AS "W3" WHICH IF FIRE |
| | RATED ACCORDING TO THE WALL SCHEDULE ON PG A-8. DOES |
| | THIS WALL REQUIRE A RATING? IF SO, PLEASE SHOW HOW |
| | OPENINGS ARE TO BE PROTECTED IN ACCORDANCE WITH FBC,M |
| | 607.1.2 & 607.1.3. IF NOT, PLEASE HAVE WALL DESIGNATION |
| | CHANGED TO A NON-RATED ASSEMBLY. |
| | |
| | 4. M-4: MECHANICAL ROOM WHERE OUTSIDE AIR AND EXHAUST |
| | AIR SHAFT IS LOCATED SHOWS AN EXTRA WALL WHICH IS NOT |
| | ON ARCITECTURAL PLAN (A-2.1A). PLEASE COORDINATE |
| | DRAWINGS. ALSO, THERE IS A 10X8 DUCT PENETRATING THE |
| | WALL BETWEEN 'MECHANICAL' AND 'VENDING'. THIS WALL |
| | APPEARS TO REQUIRE A RATING, ALTHOUGH THE WALL TYPE IS |
| | NOT SHOWN ON ARCHITECTURAL PLANS. A FIRE DAMPER IS |
| | REQUIRED AT THIS LOCATION PER FBC,M 607.1.2. |
| | |
| | 5. M-5: PLEASE SHOW SIZE OF DUCT FROM THE CORRIDOR TO |
| | RISER IN EAST STORAGE ROOM. |
| | |
| | 6. M-5 PLEASE SEE COMMENT #4, EXCEPT THE WALL IN |
| | 'MECHANICAL' IS MISSING ON THIS SHEET, BUT SHOWN ON |
| | ARCHITECTURAL (A3.1A). WHAT IS THIS WALL TYPE? ALSO, |
| | SAME FIRE DAMPER AS ABOVE IS REQUIRED. |
| | |
| | 7. M-5: 10X8 EXHAUST DUCT IS PENETRATING A RATED WALL |
| | BETWEEN ROOMS 315 AND 317. A FIRE DAMPER IS REQUIRED |
| | PER FBC,M 607.1.2. |
| | |
| | 8. M-9: FIRE DAMPER EXCEPTION AS STATED IN DETAIL #3 |
| | ONLY APPLIES IF DUCT IS ABOVE A CEILING PER FBC,M |
| | 607.1.3(3)(4). |
| | |
| | 9. THIS JOB HAS BEEN DECLARED A THRESHOLD BUILDING. AS |
| | SUCH, THE CITY OF WEST PALM BEACH REQUIRES 3 COPIES OF |
| | PLANS AND SPECIFICATIONS BE SUBMITTED FOR REVIEW. ONLY |
| | TWO COPIES OF MECHANICAL REVISIONS WERE SUBMITTED. |
| | |